49
User’s manual
3 STANDARD
APPLICATION
3.1 INPUT
3.1.1 ANALOG REFERENCE
Name
Description
Min
Max
Default
UM
Scale
KP_AI1
P01 - Corrective factor for
analog reference 1 (AUX1)
-400.0 400.0 100
%
10
OFFSET_AI1
P02 - Corrective offset for
analog reference 1 (AUX1)
-100.0
100.0
0
%
163.84
AI1
D42 - Analog Input AI1
-100
100
0
%
163.84
EN_AI1
P200 - Enable analog
reference value A.I.1
0
1
0
1
REF_AI1
D64 - Reference from Analog
Input AI1
-100 100
0
%
163.84
AI1_SEL
P203 - Meaning of analog
input A.I.1
Range
0
1
0
Speed ref.
1
Torque ref.
2
Torque limit
ref.
3
Set point PID
4
Feedback PID
5
Manual set
point PID
KP_AI2
P03 - Corrective factor for
analog reference 2 (AUX2)
-400.0
400.0
100
%
10
OFFSET_AI2
P04 - Corrective offset for
analog reference 2 (AUX2)
-100.0
100.0
0
%
163.84
AI2
D43 - Analog Input AI2
-100
100
0
%
163.84
EN_AI2
P201 - Enable analog
reference value A.I.2
0
1
0
1
REF_AI2
D65 - Reference from Analog
Input AI2
-100
100
0
%
163.84
AI2_SEL
P204 - Meaning of analog
input A.I.2
Range
1
1
0
Speed ref.
1
Torque ref.
2
Torque limit
ref.
3
Set point PID
4
Feedback PID
5
Manual set
point PID
KP_AI3
P05 - Corrective factor for
analog reference 3 (AUX3)
-400.0
400.0
100
%
10
OFFSET_AI3
P06 - Corrective offset for
analog reference 3 (AUX3)
-100.0
100.0
0
%
163.84
AI3
D44 - Analog Input AI3
-100
100
0
%
163.84
EN_AI3
P202 - Enable analog
reference value A.I.3
0
1
0
1
REF_AI3
D66 - Reference from Analog
Input AI3
-100
100
0
%
163.84
AI3_SEL
P205 - Meaning of analog
input A.I.3
Range
2
1
0
Speed ref.
1
Torque ref.
2
Torque limit
ref.
3
Set point PID
4
Feedback PID
5
Manual set
point PID
TF_TRQ_REF_AN
P206 - Filter time constant for
analog torque reference value
0.0
20.0
0
ms
10