Configuration

Weekly Schedules
The UbiquiSTAT has a total of eight customizable schedule settings that can be used to create daily, weekly, or holiday 

schedules. (By default, the UbiquiSTAT includes two schedule settings: an Occupied setting [A] at 8:00 AM Weekdays 

setting, and an Unoccupied setting [B] at 5:00 PM Weekdays setting.) You can link schedules to the any of the five 

occupancy setpoints available. You can also combine schedules with different occupancy setpoint pairs to produce up to 

eight schedule settings per day.

To create a schedule setting: 

Occupancy Schedule Screen

STEP 1  Touch the EDIT button on the Occupancy 

Schedule Entries screen.

Edit Schedule Days Screen

STEP 2  Select the days of the week you wish to assign 

the schedule to. (If desired, touch one of the 

Quick Select buttons to quickly select the 

respective days.) Touch the NEXT> button to 

bring up the EDIT SCHEDULE screen.

STEP 3  The EDIT SCHEDULE screen will display any 

previously created schedules assigned to the 

selected days. From this screen you can select 

a setpoint pair and assign it to the weekdays 

you selected, or you can touch the NEW button 

to create a new setpoint pair for the selected 

days. You can also delete a previously selected 

setpoint pair by pressing and holding the button 

for three seconds.

Edit Schedule Periods Screen

Содержание UbiquiSTAT

Страница 1: ...2800 Laura Lane Middleton WI 53562 800 288 9383 www tcsbasys com 202304 Configuration Guide UbiquiSTAT Commercial BACnet Controller...

Страница 2: ...tents 4XXX Model 1 2 4 5 Series Wired 0 Wireless 1 Standard 0 Internal Humidity Sensor 1 4X1X US4010 Series 4X2X US4020 Series 4X4X US4040 Series 4X5X US4050 Series Model Number Definitions A Key to U...

Страница 3: ...loud or TCS Insight software which is available for download on the TCS website If you have any questions regarding your UbiquiSTAT room controller contact TCS Technical Support at 800 288 9383 ext 2...

Страница 4: ...DI This allows the controller to increase the cooling setpoint and decrease the heating setpoint by a predetermined amount and effectively create a setback response to an energy demand The indicator...

Страница 5: ...inimum air circulation requirements Cool The fan runs only when there is a call for cool available only when thermostat type is conventional Choose Fan Mode Screen Fan Mode Selection Example System Mo...

Страница 6: ...east two degrees for most conditions Occupancy Schedule Settings NOTE While all UbiquiSTAT models allow you to configure weekly schedules from the touchscreen holiday schedule settings are only availa...

Страница 7: ...To create a schedule setting Occupancy Schedule Screen STEP 1 Touch the EDIT button on the Occupancy Schedule Entries screen Edit Schedule Days Screen STEP 2 Select the days of the week you wish to as...

Страница 8: ...is assigned Touch DONE to save your entry On the EDIT SCHEDULE screen touch SAVE to save the changes NOTES The first time you connect the UbiquiSTAT to Ubiquity Cloud the schedule settings will be au...

Страница 9: ...wish to attach to the new date Touch DONE to save the settings NOTE Schedule periods stay in effect until the next schedule period start time assigned to that day or until midnight at which point the...

Страница 10: ...n the SETTINGS screen brings up the first of two screens ADVANCED 1 2 has buttons for Network Settings wireless models RS 485 Network wired models Thermostat Type Analog Outputs Display Options and Te...

Страница 11: ...ettings for mode type baud rate device address and device instance Touch the SAVE button on each screen to save any changes RS 485 Communication Mode Screen RS 485 Baud Rate Screen RS 485 Network Sett...

Страница 12: ...ice Instance Number Screen BACnet Wi Fi Settings After selecting BACNET WI FI on the NETWORK SETTINGS screen touch the ENABLE SETTINGS button This will activate the screens for scanning available Wi F...

Страница 13: ...on the ADVANCED 1 2 screen allows you to configure either of the UbiquiSTAT s Analog output ports for HVAC mode to the type of action you wish to assign to the port and the range Analog Output Program...

Страница 14: ...fine tune the weighting between the internal sensor and the external sensor in five percent increments Room Temperature Source Screen Room Temperature Source Averaging Screen Temperature Sensor Calib...

Страница 15: ...D button to confirm your desire to reset the UbiquiSTAT this cannot be undone You will then return to the INITIAL SETUP screen at the beginning of the Startup Wizard refer to the UbiquiSTAT Quick Setu...

Страница 16: ...l logic is disabled and outputs will revert to inactive or zero percent inputs Relay Inputs W1 W2 Y1 Y2 G B O TC Touching the Relay Outputs buttons activates the connected equipment after a three seco...

Страница 17: ...eported when the UbiquiSTAT detects an unexpected behavior Report any faults to TCS technical support System Event Log Screen Internal Dehumidification Sensor Programming Touching the DEHUMIDIFICATION...

Страница 18: ...up the Status section from which you can verify all settings in real time The screens in this section are grouped into three categories System Advanced and Network The information on each screen vari...

Страница 19: ...l sensors e g outside temperature humidity CO2 etc NOTES Inputs for Mixed Air and CO2 are only available on 4X4X 4X5X Input for Humidity is only available on 4X5X Relay Outputs The current state of he...

Страница 20: ...update the status About Section Touching the ABOUT button on the bottom of the HOME screen brings up the About section The main About screen displays the following information Model number Device Name...

Страница 21: ...or value when its signal is at the maximum range 20mA Reference BACnet IDs AV 162 AV 164 In addition there are four read only analog BACnet objects which display the raw readings and the engineering s...

Страница 22: ...is showing on display Faulty wiring Faulty relay Room temperature is above the cooling setpoint or below the heating setpoint Check wiring Check for a relay failure by connecting a jumper across termi...

Страница 23: ...ing and cooling setpoints are correct Reset the UbiquiSTAT by touching and holding the STATUS button for five seconds Analog outputs not working Faulty wiring Improper programming UbiquiSTAT is being...

Отзывы: