3

MOUNTING

 

& WIRING

Mounting

The QWL 3 .1 Rev 3 Series Panel is designed for mounting us-

ing four #10 pan head screws. When drilling, ensure that the 

QWL 3 .1 Rev 3 Series Panel is powered down and all metal 

shavings are captured .

Wiring

The QWL 3 .1 Rev 3 Series Panel terminal designations are 

shown below.

INPUT WIRING

The QWL 3 .1 Rev 3 Series Panel accepts two 0 to 5 VDC 

inputs, 8 dry contact/digital inputs and 4 pulse meter 

inputs .  

POWERING THE QWL 3.1 REV 3 SERIES PANEL

The QWL 3 .1 Rev 3 Series Panel is powered from a 

120VAC @ 60HZ to 12VDC power supply module (includ

-

ed) . The QWL 3 .1 Rev 3 Series Panel is designed to con-

tain 24 VAC devices and wiring ONLY . No line voltage (120 

VAC or greater) is to be installed within this panel.

Main Board

Main Board

1" EMT Knockout for use

with ¾" Conduit

NOTE: 

If drilling, the QWL 

3.1 Rev 3 Series 

Panel must be 

powered down and 

metal shavings 

must be contained. 

DI8 DI7           DI6 DI5                                                         DI4 DI3           DI2 DI1

See RS-485 controller 

network wiring diagram .

QWL 3.1 REV 3 SERIES PANEL WIRING 

QWL 3.1 REV 3 SERIES PANEL LAYOUT

Содержание QWL 3.1 Rev 3

Страница 1: ...x 608 836 9044 www tcsbasys com Rev 0617 PRODUCT MANUAL The QWL 3 1 Rev 3 Integrated Building Manager Panel contains a Ubiquity Cloud Site Gateway w integrated lighting and energy management controls...

Страница 2: ...METER SEQ100 Utility Pulse Counting Meter for Monitoring of Electric single and 3 phase kW and kWh Gas Water BT LIGHTING CONTROLLER SLQ218 365 day programming for each circuit Analog input for photo...

Страница 3: ...y contact digital inputs and 4 pulse meter inputs POWERING THE QWL 3 1 REV 3 SERIES PANEL The QWL 3 1 Rev 3 Series Panel is powered from a 120VAC 60HZ to 12VDC power supply module includ ed The QWL 3...

Страница 4: ...wire a 120 terminating resis tor across the A and B terminals at the QWL 3 1 Rev 3 Series Panel See 1 below If the QWL 3 1 Rev 3 Series Panel will be in the middle of the network do not wire in the te...

Страница 5: ...ormation in this section click the Update Installation Info button RS 485 Network Port Configuration Configure each of the detected COM ports for this site Typically you will leave Auto Detection of C...

Страница 6: ...ng Info button SECURITY INFORMATION This section contains settings which control the security of the gateway within the QWL 3 1 Rev 3 Series Panel and whether or not it can be accessed through the web...

Страница 7: ...must be programed using TCS Insight or Ubiquity Cloud CHANNEL EVENT SCHEDULING There are eight independent channels each with its own schedule If the occupied or ON time for a particular day is from...

Страница 8: ...ng channels Enable AI2 Threshold checkboxes and enter a threshold and a hysteresis to be used If AI1 is not used the channel power threshold MUST equal the scaling high limit Select whether you want t...

Страница 9: ...cal time calculation Next select the channel s that should have the astronom ical time function and click the Enable box This is done in the Schedule section of the page Note For non North American Da...

Страница 10: ...CT or on the utility output meter This value is only used for and electric meter P REV The Pulses per revolution for the meter This value is usually provided from the utility company CONSTANT The val...

Страница 11: ...e to check and verify all wiring before powering up the QWL 3 1 Rev 3 Series Panel The QWL 3 1 Rev 3 Series Panel is designed to contain 24 VAC devices and wiring ONLY No line voltage 120 VAC or great...

Страница 12: ...rify that the power supply nodule included with the QWL 3 1 Rev 3 Series Panel is plugged in to an outlet that has power IF THEN Check that the baud rate set on the controller s are all set the same V...

Отзывы: