background image

2800 Laura Lane • Madison, WI 53562  |  800.288.9383 • fax: 608.836.9044  |  www.tcsbasys.com  

10

11

COMISSIONING

 

& PROGRAMMING

factor is 4 .4 If the line voltage is 277 VAC and the SLQ218 

power input is 24 VAC, then the calibration factor is 11.5.

DAYLIGHT SAVING TIME

If Daylight saving is used, simply enable the “Daylight Sav

-

ing Time”  option within the software and enter the starting 

month + week and the ending month + week .

Programming - Pulse Meter

The utility pulse meter module portion of this panel is an 

SEQ100.

METER INPUTS

There are four meter inputs available. Each one is setup for 

a dry contact and cannot be changed. Each input (Meter 1, 

Meter 2, Meter 3 & Meter 4) can be configured to accept 

signals representing electrical, BTU, water or gas usage. 

The required parameters will be provided by either the 

utility company involved or on the current transducer (CT) 

used to generate the pulse signal .

METER TYPES

The SEQ100 supports various meter types . Selecting a 

meter type changes the default values as they are used to 

calculate meter consumption and demand for that particu-

lar meter. For each of the four SEQ100 meter inputs, there 

are five selectable options: 
 

ELEC 1 PH: Electric single phase meter.

 

ELEC 3 PH: Electric three phase meter.

 

GAS: Gas meter .

 

WATER: Water meter

 

BTU: BTU meter

Utility pulse meters can be one of two different types, 

depending on whether they count the leading and trailing 

edges of the pulse or only the leading edge of the pulse as 

If you have a Type C device (3 terminals KYZ), you will 

need to double the multiplier. The SEQ100 only counts the 

contact closures for the K and Z terminals. Doubling the 

multiplier will correct this problem.

PROGRAMMING THE METER CONSTANTS:

CT Value: The value of the CT wired to the meter . This 

value is usually provided on the CT or on the utility output 

meter . This value is only used for and electric meter .
P/REV:  The Pulses per revolution for the meter . This value 

is usually provided from the utility company .  
CONSTANT: The value of the constant for the meter is usu-

ally provided from the utility company and many times is 

located on the electric or gas bill.  
CU FT/P: The value for Cubic Feet per pulse. This only 

applies to Water, GAS and BTU, and is usually found on the 

utility meter itself . 

MULT: The multiplier for the meter can be used to scale 

the meter output or correct for KYZ meter . The multiplier 

is used to convert the pulses to engineering unit data . For 

example, if your meter provides one pulse per 0.01KWH, 

then a constant of 0.01 is required.

MULTIPLIER:

Each model of power meter is different and has a different 

multiplier. For example, if the meter is a Type A and reports 

1/10 kWh per pulse, set the input multiplier to 0.1. If the 

meter is a Type C and reports 1/10 kWh per pulse, set the 

input multiplier to 0 .2 .

a single count. A pulse output can be either a mechanical 

relay or solid state device . The pulse output corresponds 

to a unit/time of a monitored quantity. The amount of time 

between states of a pulse output corresponds to the meter 

demand and the number of pulses is proportional to the 

meter’s consumption. 

Below is a diagram depicting two types of utility meter 

pulse outputs . Meter Type A counts only the leading 

edge as a single pulse and the trailing edge is ignored . 

Meter Type C is known as a true KYZ meter and counts 

both the leading and trailing edges as a pulse, effectively 

doubling the number of pulses as seen by Meter Type A. 

The SEQ100 measures Type A output only; however, KYZ 

functionality can be mimicked by using a “Meter Multiplier” 

value of 2 .

In the following picture, both Type A and C are shown. 

Three pulses are shown, labelled 1, 2, and 3. Notice how 

the Type A output closes and opens for each pulse, where 

the Type C output simply changes state .

Содержание QWL 3.1 Rev 3

Страница 1: ...x 608 836 9044 www tcsbasys com Rev 0617 PRODUCT MANUAL The QWL 3 1 Rev 3 Integrated Building Manager Panel contains a Ubiquity Cloud Site Gateway w integrated lighting and energy management controls...

Страница 2: ...METER SEQ100 Utility Pulse Counting Meter for Monitoring of Electric single and 3 phase kW and kWh Gas Water BT LIGHTING CONTROLLER SLQ218 365 day programming for each circuit Analog input for photo...

Страница 3: ...y contact digital inputs and 4 pulse meter inputs POWERING THE QWL 3 1 REV 3 SERIES PANEL The QWL 3 1 Rev 3 Series Panel is powered from a 120VAC 60HZ to 12VDC power supply module includ ed The QWL 3...

Страница 4: ...wire a 120 terminating resis tor across the A and B terminals at the QWL 3 1 Rev 3 Series Panel See 1 below If the QWL 3 1 Rev 3 Series Panel will be in the middle of the network do not wire in the te...

Страница 5: ...ormation in this section click the Update Installation Info button RS 485 Network Port Configuration Configure each of the detected COM ports for this site Typically you will leave Auto Detection of C...

Страница 6: ...ng Info button SECURITY INFORMATION This section contains settings which control the security of the gateway within the QWL 3 1 Rev 3 Series Panel and whether or not it can be accessed through the web...

Страница 7: ...must be programed using TCS Insight or Ubiquity Cloud CHANNEL EVENT SCHEDULING There are eight independent channels each with its own schedule If the occupied or ON time for a particular day is from...

Страница 8: ...ng channels Enable AI2 Threshold checkboxes and enter a threshold and a hysteresis to be used If AI1 is not used the channel power threshold MUST equal the scaling high limit Select whether you want t...

Страница 9: ...cal time calculation Next select the channel s that should have the astronom ical time function and click the Enable box This is done in the Schedule section of the page Note For non North American Da...

Страница 10: ...CT or on the utility output meter This value is only used for and electric meter P REV The Pulses per revolution for the meter This value is usually provided from the utility company CONSTANT The val...

Страница 11: ...e to check and verify all wiring before powering up the QWL 3 1 Rev 3 Series Panel The QWL 3 1 Rev 3 Series Panel is designed to contain 24 VAC devices and wiring ONLY No line voltage 120 VAC or great...

Страница 12: ...rify that the power supply nodule included with the QWL 3 1 Rev 3 Series Panel is plugged in to an outlet that has power IF THEN Check that the baud rate set on the controller s are all set the same V...

Отзывы: