COMMISSIONING
TOOLS
Commissioning Tools
A separate page which contains various commissioning tools can be accessed by clicking the “Commissioning Tools”
button at the bottom of the Setup page. This page gives you access to additional information about the connection
status of the QD2040c and the controller network connected to it.
UBIQUITY CONNECTION STATUS
This section displays the status of the connection between the QD2040c and the central server. You have three options
for the message that will appear here:
1)
Error
- No Route to Host -- means the unit does not currently have an Ethernet connection.
2)
Connected
-- means the unit is able to communicate to the Ubiquity central server BUT is not being matched up with a
specific Site, typically this indicates that the site is not initialized on the central server side yet, please contact TCS Basys
Controls to assign or initialize the QD2040c to a site
3)
Established
-- means the unit is communicating with the Ubiquity central server AND is ready to go. All Ubiquity
functions (monitoring, programming, alarming, etc.) should be available through the user interface at this point.
Clicking the green button with the arrow on it on the right side of the Ubiquity Connection Status title bar will refresh the
connection status