7.4.1.3 Zero-crossing signal detection error diagnosis and solution.
Malfunction conditions
When PCB does not receive zero crossing signal feedback for
4 minutes or the zero crossing signal time interval is abnormal.
Potential causes
●
Connection mistake
●
Faulty PCB
Trouble shooting:
Check if the connections and
power supply is normal?
Correct the connections. Turn on the
unit when the power supply is good.
No
Yes
Indoor main PCB is
defective. Replace indoor
main PCB.
PIC 4: Check point button, press 1 time for check
how many indoor units are connected.
Содержание MMCUT18AS2
Страница 3: ...3 MMCUT36AS4 WD30 metal plate 114 MMCUT48AS5 WE30 metal plate 121...
Страница 10: ...10...
Страница 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor MMCUT18AS2...
Страница 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor MMCUT27AS3...
Страница 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor MMCUT36AS4...
Страница 29: ...29...
Страница 43: ...43 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Страница 44: ...44 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 59: ...59 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Страница 60: ...60 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 66: ...66 IPM board for 2 zone 3 zone...
Страница 68: ...68 IPM board for 4 zone...
Страница 71: ...71 Two ports of the inductance Inductance...
Страница 74: ...74 Vs Vcc Vsp FG...
Страница 77: ...77...
Страница 80: ...80...
Страница 83: ...83...
Страница 94: ...94 6 EXV check Disconnect the connectors...
Страница 95: ...95 Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 96: ...96 Red Blue Red Yellow...
Страница 97: ...97 Brown Orange...
Страница 98: ...98 Brown White...
Страница 108: ...108 Screws of right rear panel Screws of terminal board...