21
T3
Increase fan speed increase
Keep current fan speed
Decrease fan speed
Fan stop
LowCoolT3_ON
LowCoolT3_Down
LowCoolT3_OFF
5.4.3.2 Heating Mode
Under normal operating conditions, the system
chooses a running fan speed according to
ambient temperature:
Outdoor temperature℃
21
Breeze fan speed
19
18
Supper low fan speed
16
15
Low fan speed
13
12
Middle fan speed
10
0
High fan speed
-2
Supper high fan speed
5.4.4 Electronic Expansion Valve (EXV)
Control
1. EXV remains fully closed while the device is
powering up. EXV then remains on standby with
350P open. It opens to the target angle after the
compressor starts.
2. EXV closes with -
160P when
the compressor
stops. Then it remains on standby with 350P
open. It opens to the target angle after the
compressor starts.
3. The action priority for the EXVs is A-B-C-D-E.
4. The compressor and outdoor fan commence
operation only after EXV initializes.
5.4.4.1 Cooling Mode
The initial open angle of the EXV depends on the
size of the indoor model. The adjustment range is
100-400p.
When the unit has been running for 3 minutes,
the outdoor receives indoor units' capacity
demand and T2B information and then calculates
their average. After comparing each indoor’s T2B
with the average, the outdoor gives the following
modification commands:
---- If the T2B
>
average, the relevant valve needs
to open
16p
more
---- If the T2B= average, the relevant valve’s open
range remains as is
---- If the T2B
<
average, the relevant valve needs
to close
16p
more
This modification is carried out every 2 minutes.
5.4.4.2 Heating Mode
The initial open angle of the EXV depends on the
size of the indoor model. The adjustment range is
150-350p.
When the unit has been running for 3 minutes,
the outdoor unit receives the indoor units' indoor
units' capacity demand and T2 information and
then calculates their average.
After comparing each indoor unit’s T2 with the
average, the outdoor gives the following
modification commands:
----If the T2
>
2, the relevant valve
needs to close
16p
more
----
If 2≥the T2≥ average
-2, the relevant
valve’s open range remains as is
----If the T2
<
average-2, the relevant valve needs
to open
16p
more
This modification is carried out every 2 minutes.
Содержание MMCUT18AS2
Страница 3: ...3 MMCUT36AS4 WD30 metal plate 114 MMCUT48AS5 WE30 metal plate 121...
Страница 10: ...10...
Страница 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor MMCUT18AS2...
Страница 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor MMCUT27AS3...
Страница 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor MMCUT36AS4...
Страница 29: ...29...
Страница 43: ...43 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Страница 44: ...44 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 59: ...59 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Страница 60: ...60 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 66: ...66 IPM board for 2 zone 3 zone...
Страница 68: ...68 IPM board for 4 zone...
Страница 71: ...71 Two ports of the inductance Inductance...
Страница 74: ...74 Vs Vcc Vsp FG...
Страница 77: ...77...
Страница 80: ...80...
Страница 83: ...83...
Страница 94: ...94 6 EXV check Disconnect the connectors...
Страница 95: ...95 Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 96: ...96 Red Blue Red Yellow...
Страница 97: ...97 Brown Orange...
Страница 98: ...98 Brown White...
Страница 108: ...108 Screws of right rear panel Screws of terminal board...