19
Note:Average value of T2
:
Sum T2 value of all
indoor units)/ (indoor units number
℃
T2 average
Decrease frequency
47
Keep frequency
40
Increase frequency
Use the following table and final capacity
request to confirm the operating frequency.
Frequency
(Hz)
0
HEAT
_F1
HEAT
_F2
…
HEAT
_F24
HEAT
_F25
Amendatory
capacity
demand.
0
1
2
…
24
25
The maximum running frequency is adjusted
according to the outdoor ambient temperature
℃
34
33
Standby
28
27
Fmax=T4FREHEATMAX1
25
24
Fmax=T4FREHEATMAX2
22
21
Fmax=T4FREHEATMAX3
19
18
Fmax=T4FREHEATMAX4
17
16
Fmax=T4FREHEATMAX5
15
14
Fmax=T4FREHEATMAX6
12
11
Fmax=T4FREHEATMAX7
6
5
Fmax=T4FREHEATMAX8
1
0
Fmax=T4FREHEATMAX9
-3
-4
Fmax=F21
-7
-8
Fmax=F22
-11
-12
Fmax=F23
-15
-16
Fmax=F24
Fmax=F25
5.4.2 Defrosting Control
Conditions for Defrosting:
After the compressor starts and enters normal
operation, mark the minimum value of T3 from
the 10th to 15th minute as T30.
If any one of the following conditions is satisfied,
the unit enters defrosting mode:
1) If the compressor’s cumulative running time
reaches 29 minutes and T3< TCDI1 and T3
+
T30SUBT3ONE
≦
T30.
2) If the compressor cumulative running time
reaches 35 minutes and T3< TCDI2 and T3
+
T30SUBT3TWO
≦
T30.
3) If the compressor cumulative running time
reaches 40 minutes and T3< -24C for 3 minutes.
Содержание MMCUT18AS2
Страница 3: ...3 MMCUT36AS4 WD30 metal plate 114 MMCUT48AS5 WE30 metal plate 121...
Страница 10: ...10...
Страница 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor MMCUT18AS2...
Страница 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor MMCUT27AS3...
Страница 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor MMCUT36AS4...
Страница 29: ...29...
Страница 43: ...43 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Страница 44: ...44 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 59: ...59 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Страница 60: ...60 PIC3 Main board LED when power on and unit standby Pic 2 IPM for5 zone Power Standby Operating...
Страница 66: ...66 IPM board for 2 zone 3 zone...
Страница 68: ...68 IPM board for 4 zone...
Страница 71: ...71 Two ports of the inductance Inductance...
Страница 74: ...74 Vs Vcc Vsp FG...
Страница 77: ...77...
Страница 80: ...80...
Страница 83: ...83...
Страница 94: ...94 6 EXV check Disconnect the connectors...
Страница 95: ...95 Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 96: ...96 Red Blue Red Yellow...
Страница 97: ...97 Brown Orange...
Страница 98: ...98 Brown White...
Страница 108: ...108 Screws of right rear panel Screws of terminal board...