TCL Air Conditioner Service Manual
39
According to the following table to flare the pipe
Pipe diameter
Flare dimension A (mm)
Flare shape
Min
Max
1/4" (6.35)
8.3
8.7
R0.4~0.8
A
45°
90
°
4
-+
3/8" (9.52)
12.0
12.4
1/2" (12.7)
15.4
15.8
5/8" (15.9)
18.6
19.1
3/4" (19)
22.9
23.3
After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct
or exogenous impurity come into the pipe.
2.6.3.7 Bending Pipes
(1) The pipes are shaped by your hands. Be careful not to collapse them.
(2) Do not bend the pipes in an angle more than 90°.
(3) When pipes are repeatedly bent or stretched, the material will harden, making it difficult to
bend or stretch them any more . Do not bend or stretch the pipes more than three times.
(4) When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the
heat insulating pipe with a sharp cutter as shown in Figure 3-3-3, and bend it after exposing the pipe.
After bending the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and
secure it with tape.
NOTE
:
①
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of
150mm (5-7/8inch) or over.
②
If the pipe is bent repeatedly at the same place, it will break.
2.6.3.8 Drill Holes if the Pipes Need to Pass the Wall.
2.6.3.9 According to the Field Condition to Bend the Pipes so that It Can Pass the Wall
Smoothly.
2.6.3.10 Set the Wall Conduit.
2.6.3.11 Set the Supporter for the Pipe.
2.6.3.12 Locate the Pipe and Fix It by Supporter.
For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
Содержание TCC-09C2HRH/DV
Страница 7: ...TCL Air Conditioner Service Manual 7 MODEL TCC 18C2HRH DV PCB EEV...
Страница 26: ...TCL Air Conditioner Service Manual 26...
Страница 27: ...TCL Air Conditioner Service Manual 27...
Страница 28: ...TCL Air Conditioner Service Manual 28...
Страница 29: ...TCL Air Conditioner Service Manual 29...
Страница 30: ...TCL Air Conditioner Service Manual 30...