TCL Air Conditioner Service Manual 

c o m p r e s s o r

4 - w a y   v a lv e

o u t d o o r   fa n   m o t o r

1 0 m

O N

O F F

O N

O F F
O N
O F F

2 0 s

1 0 s

2 0 s

1 0 s

 

 

In defrosting, LED showing by winking. 
Come into or out of defrosting, indoor fan motor speed is the same as Cold Air Prevention 
Control. 
One of the following conditions is satisfied, unit come out of defrosting and shift to heating 
mode: 
    a. Outdoor coil Temperature (OPT) 

15

 

       

b. Defrost time keep time for more than 10 minutes. 

(

5

) Indoor exchanger overheat protection 

 When Indoor exchanger Temperature(IPT) is higher than 55

,

 unit come into indoor 

exchanger overheat protection. Compressor drop its frequency toward to F1 level until IPT

52

; If IPT

52

 and keep for 5 minutes , control system don’t limit running frequency. 

 If IPT>62

,

 control system shut down compressor, and recover when IPT drop less than 50

.

   

6.  “SLEEP” mode 

When the SLEEP button is pressed, the SLEEP mode is selected as following: 

z

  The indoor fan speed is set at low speed, the power lamp and the sleep lamp is on, the 

display of temperature will be close after 5 minutes.

 

z

  When selecting COOLING/DRY operation with SLEEP mode, the set temperature will be 

raised by 1

 1 hour later and by 2

 2 hour later. 

z

  When selecting HEATING operation with SLEEP mode, the set temperature will be dropped 

by 1

 1 hour later and 2

 2hour later. 

z

  After the System operates in SLEEP mode for 8 hours, it will stop automatically. 

7.   EMERGENCY Operation 

When the EMERGENCY Operation switch is pressed once, COOLING mode is selected and if 
in 3 seconds the EMERGENCY Operation switch is pressed again, mode is selected. Then 
pressed once again, the unit is switch off. 
When the remote controller is missing, has failed or the batteries run down, press the 
EMERGENCY Operation switch on the front of the indoor unit. The unit will start. 
The first 30 minutes of operation will be the test run operation. The operation is for servicing. 
The indoor fan runs at high speed and the system is in continuous operation. The thermostat is 
ON and the timer is reset to normal. 
After 30 minutes of test run operation the system shifts to AUTO COOLING/HEATING mode, 
and the indoor fan runs in automatic speed. The operation continues unit the EMERGENCY 
operation switch is pressed or a button on the remote controller is pressed, the normal 
operation will start. 
NOTE: Do not press the EMERGEMCY Operation switch during normal operation. 

8. AUTO-RESTART Function (Option)

 

1. When air conditioner is operating in one mode, all of its operation data, such as working 
mode and temperature of setup would be memorized into IC by main PCB. If power cuts due to 

                                                                                           

 

8

 

Содержание TAC-09CHSA/GI

Страница 1: ...PE AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 11 5 EXPLOSION VIEW 12 6 PARTS LIST 13 Models TAC 09CHSA GI TAC 12CHSA GI TCL SERVI...

Страница 2: ...formation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior n...

Страница 3: ...H x D Outdoor mm 760 560 260 760 560 260 Indoor kg 8 5 8 5 Outdoor kg 30 34 Packing dimensions Indoor mm 883 325 271 883 325 273 W x H x D Outdoor mm 863 598 381 863 598 383 Indoor kg 10 5 10 5 Outdoo...

Страница 4: ...ler 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Страница 5: ...is overload controller shut down the unit immediately and show error code 6 Compressor abnormity protection When compressor start on or in the process of running if there is no feedback to controller...

Страница 6: ...or will run automatically 3 Auto fan control in cooling mode In cooling mode include cooling in I feel mode fan speed is determined by t as the following diagram 1 5 1 0 3 0 3 5 t come down high fan t...

Страница 7: ...ocess of defrosting 4 Defrosting Defrosting is controlled by the microprocessor When one of the following conditions is satisfied unit will come into defrosting a Outdoor heat exchanger Temperature OP...

Страница 8: ...later z When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 2hour later z After the System operates in SLEEP mode for 8 hours it will stop auto...

Страница 9: ...of the error list z Protection display function can be selected in hardware and the default don t display z To insure of in and out communist is credibility the failures relate to outdoor unit will r...

Страница 10: ...tdoor power board when compressor is running it is normally light when no feedback of signal to power board from compressor it will wink by lighting 1s and going out 1s If failures happened it will li...

Страница 11: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA GI TAC 12CHSA GI Indoor unit Outdoor Unit 11...

Страница 12: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Indoor unit Model TAC 09CHSA GI TAC 12CHSA GI 12...

Страница 13: ...filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal 1...

Страница 14: ...r filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal...

Страница 15: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Outdoor unit Model TAC 09CHSA GI TAC 12CHSA GI 15...

Страница 16: ...necting pipe 1 15 1120250425 Suction pipe 1 16 1120250426 Discharge pipe 1 17 1120250428 Condenser connecting pipe 1 18 1120250615 Capillary assembly 1 19 1140020011 Sound arrester 1 750 350 8 20 1080...

Страница 17: ...nual 17 PART LIST Outdoor unit Model TAC 09CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Страница 18: ...pipe 1 15 1120321529 Suction pipe 1 16 1120321530 Discharge pipe 1 17 1120321532 Condenser connecting pipe 1 18 1120321525 Capillary assembly 1 19 1140020011 Sound arrester 750 350 8 1 20 1080050002 R...

Страница 19: ...nual 19 PART LIST Outdoor unit Model TAC 12CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Отзывы: