TCL Air Conditioner Service Manual 

Electronic Controller 

1. Safety 

Protection 

(1)  Time Delay for Safety protection 

z

  3 minutes delay for compressor ---The compressor is ceased for 3minutes before 

restarting to balance the pressure in the refrigeration cycle in order to protect the 
compressor. 

z

  2 minutes delay for 4-way valve---The 4-way valve will be ceased for 2 minutes late 

after compressor to prevent the refrigerant-gas abnormal noise when the HEATING 
operation is OFF or switch to the other operation mode. 

(2)  Discharge temperature protection 

There is a temperature sensor on top of compressor, when temperature on top of 
compressor exceeded the limit, system control will shut down the compressor and the 
display board will show the error code.   

(3)    lower voltage protection 

When AC voltage 

158V and keep it for 10 seconds, unit will be shut down for protection. 

(4)  Over voltage protection 

When AC voltage 

260V, unit will be shut down and recover while AC

255V. 

(5)  Over current protection 

When the current of outdoor unit is overload, controller shut down the unit immediately and 
show error code. 

(6) Compressor abnormity protection 

When compressor start on or in the process of running, if there is no feedback to controller 

or load of compressor is abnormity, the air conditioner will shut down, and show error 
code.  

(7) 

IPM

 module protection 

IPM module has high temperature & over current protection itself, if there is signal 

feedback to IPM, the outdoor unit will shut down, LED on outdoor PCB will show the error 
code. 

2.    “I Feel” Mode Operation 

(1) When the “I Feel” mode is selected, the operation mode and initial temperature set are 

determined by the initial room temperature at start-up of the operation except to turn off the 
air conditioner and operates it again. 

(2)  If the mode is change to “I Feel” from other mode, the “I Feel” mode doesn’t operate until 

compressor stop for more than 3 minutes. 

 

Mode 

Initial Room Temperature 

Initial Set Temperature   

COOLING 

RT

26

 23

 

DRY 

26

℃>

RT

20

 RT-2

 

HEATING for Heat Pump 

FAN for Cooling Only 

RT

20

 - 

 

z

  In the “I Feel” mode, when the controller receives the up or down sig

na

l

 

of temperature, 

the set temperature can adjust by 1

 upper or lower. The biggest you can adjust by 

2

 upper or lower. 

 

3.  “COOLING” Mode Operation 

                                                                                           

 

5

 

Содержание TAC-09CHSA/GI

Страница 1: ...PE AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 11 5 EXPLOSION VIEW 12 6 PARTS LIST 13 Models TAC 09CHSA GI TAC 12CHSA GI TCL SERVI...

Страница 2: ...formation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior n...

Страница 3: ...H x D Outdoor mm 760 560 260 760 560 260 Indoor kg 8 5 8 5 Outdoor kg 30 34 Packing dimensions Indoor mm 883 325 271 883 325 273 W x H x D Outdoor mm 863 598 381 863 598 383 Indoor kg 10 5 10 5 Outdoo...

Страница 4: ...ler 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Страница 5: ...is overload controller shut down the unit immediately and show error code 6 Compressor abnormity protection When compressor start on or in the process of running if there is no feedback to controller...

Страница 6: ...or will run automatically 3 Auto fan control in cooling mode In cooling mode include cooling in I feel mode fan speed is determined by t as the following diagram 1 5 1 0 3 0 3 5 t come down high fan t...

Страница 7: ...ocess of defrosting 4 Defrosting Defrosting is controlled by the microprocessor When one of the following conditions is satisfied unit will come into defrosting a Outdoor heat exchanger Temperature OP...

Страница 8: ...later z When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 2hour later z After the System operates in SLEEP mode for 8 hours it will stop auto...

Страница 9: ...of the error list z Protection display function can be selected in hardware and the default don t display z To insure of in and out communist is credibility the failures relate to outdoor unit will r...

Страница 10: ...tdoor power board when compressor is running it is normally light when no feedback of signal to power board from compressor it will wink by lighting 1s and going out 1s If failures happened it will li...

Страница 11: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA GI TAC 12CHSA GI Indoor unit Outdoor Unit 11...

Страница 12: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Indoor unit Model TAC 09CHSA GI TAC 12CHSA GI 12...

Страница 13: ...filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal 1...

Страница 14: ...r filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal...

Страница 15: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Outdoor unit Model TAC 09CHSA GI TAC 12CHSA GI 15...

Страница 16: ...necting pipe 1 15 1120250425 Suction pipe 1 16 1120250426 Discharge pipe 1 17 1120250428 Condenser connecting pipe 1 18 1120250615 Capillary assembly 1 19 1140020011 Sound arrester 1 750 350 8 20 1080...

Страница 17: ...nual 17 PART LIST Outdoor unit Model TAC 09CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Страница 18: ...pipe 1 15 1120321529 Suction pipe 1 16 1120321530 Discharge pipe 1 17 1120321532 Condenser connecting pipe 1 18 1120321525 Capillary assembly 1 19 1140020011 Sound arrester 750 350 8 1 20 1080050002 R...

Страница 19: ...nual 19 PART LIST Outdoor unit Model TAC 12CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Отзывы: