TCL Air Conditioner Service Manual 

(1) Compressor frequency control 

           

According to difference room temperature and set temperature(

δ

t = RT-ST

), running 

frequency of compressor is controlled by electronic controller. When room temperature is much 
higher than set temperature, compressor will start at a high frequency, and as room temperature 
goes down, compressor running frequency will go down. When room temperature is lower than set 
temperature, compressor will run at very low frequency. In general, unit will change its running 
frequency according to

δ

to make room temperature closing to set temperature.   

(2)  Outdoor temperature affects running frequency of compressor 

Outdoor temperature affect compressor’s running frequency. Difference inlet temperature of 

outdoor unit is adapted by difference compressor running frequency. While outdoor temperature is 
about 30

, the compressor will run in high frequency.   

        If unit run in “cooling” mode and outdoor temperature is less than -1

℃,

controller will shut down 

compressor and show error code, while the ambient temperature is over 0

℃,

 the compressor will 

run automatically

.

 

(3)  Auto fan control in cooling mode 

   In cooling mode (include cooling in “I feel” mode), fan speed is determined by 

δ

t

, as the 

following diagram:   

1.5

1.0

3.0

3.5

δ

t come down

high fan

δ

t come up

midium fan

low fan

RT-ST

 

4. “DRY” 

Mode 

Operation 

(1) The system for DRY operation used the same refrigerant circle as the cooling one. 
(2) 

When the system operates in DRY mode, at first it operates in cooling mode at 16

 or 

18

 for 3 minutes. After that, the system will operate in cooling mode with lowest fan 

speed, meanwhile the set temperature (

ST

) is “RT-2

 which means that the ST is room 

temperature at then minus 2. During the course of this mode, the fan speed set operation 
and room temperature set are restricted, except the vane motor adjusting. 

5.    “HEATING” Mode Operation (available for Heat Pump only) 

(1)

 Frequency control 

The same as the frequency control in cooing mode, running frequency of compressor is 
controlled by controller. Unit change its running frequency according to 

δ

to make room 

temperature closing to the set temperature.     

(2)

  Indoor fan motor control 

1.  Cold Air Prevention Control 

z

  The function is intended to prevent cold air from being discharged when the heating 

operation starts or when defrosting. 

z

  The indoor fan speed will be controlled as following. 

 
 

                                                                                           

 

6

 

Содержание TAC-09CHSA/GI

Страница 1: ...PE AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 11 5 EXPLOSION VIEW 12 6 PARTS LIST 13 Models TAC 09CHSA GI TAC 12CHSA GI TCL SERVI...

Страница 2: ...formation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior n...

Страница 3: ...H x D Outdoor mm 760 560 260 760 560 260 Indoor kg 8 5 8 5 Outdoor kg 30 34 Packing dimensions Indoor mm 883 325 271 883 325 273 W x H x D Outdoor mm 863 598 381 863 598 383 Indoor kg 10 5 10 5 Outdoo...

Страница 4: ...ler 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Страница 5: ...is overload controller shut down the unit immediately and show error code 6 Compressor abnormity protection When compressor start on or in the process of running if there is no feedback to controller...

Страница 6: ...or will run automatically 3 Auto fan control in cooling mode In cooling mode include cooling in I feel mode fan speed is determined by t as the following diagram 1 5 1 0 3 0 3 5 t come down high fan t...

Страница 7: ...ocess of defrosting 4 Defrosting Defrosting is controlled by the microprocessor When one of the following conditions is satisfied unit will come into defrosting a Outdoor heat exchanger Temperature OP...

Страница 8: ...later z When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 2hour later z After the System operates in SLEEP mode for 8 hours it will stop auto...

Страница 9: ...of the error list z Protection display function can be selected in hardware and the default don t display z To insure of in and out communist is credibility the failures relate to outdoor unit will r...

Страница 10: ...tdoor power board when compressor is running it is normally light when no feedback of signal to power board from compressor it will wink by lighting 1s and going out 1s If failures happened it will li...

Страница 11: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA GI TAC 12CHSA GI Indoor unit Outdoor Unit 11...

Страница 12: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Indoor unit Model TAC 09CHSA GI TAC 12CHSA GI 12...

Страница 13: ...filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal 1...

Страница 14: ...r filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal...

Страница 15: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Outdoor unit Model TAC 09CHSA GI TAC 12CHSA GI 15...

Страница 16: ...necting pipe 1 15 1120250425 Suction pipe 1 16 1120250426 Discharge pipe 1 17 1120250428 Condenser connecting pipe 1 18 1120250615 Capillary assembly 1 19 1140020011 Sound arrester 1 750 350 8 20 1080...

Страница 17: ...nual 17 PART LIST Outdoor unit Model TAC 09CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Страница 18: ...pipe 1 15 1120321529 Suction pipe 1 16 1120321530 Discharge pipe 1 17 1120321532 Condenser connecting pipe 1 18 1120321525 Capillary assembly 1 19 1140020011 Sound arrester 750 350 8 1 20 1080050002 R...

Страница 19: ...nual 19 PART LIST Outdoor unit Model TAC 12CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Отзывы: