6. FAQ
6.1 Error code
6.1.1 Inverter Error
No.
Error Code
Description
Solution
101
U_Bus_OV
DC bus is over voltage
Check the battery voltage.
102
U_Bus_LV
DC bus is under voltage
Check the battery connection and
voltage.
103
U_Bus_HW_Pro
Hardware protection against
DC bus over voltage
Check the battery voltage and the
charger output voltage
104
PSU_Fault
Auxiliary power supply is
abnormal
Restart the inverter. Contact your
installer if it still exists.
105
T_HS_OT
Heat sink's temperature is
too high
Check and assure inverter has
good ventilation
106
T_TX_OT
Transformer's temperature
is too high
Too high ambient temperature.
107
Sam_HD_Fault
Sampling is abnormal
Restart the inverter. Contact your
installer if it still exists.
108
EEPROM_Fail
ROM is abnormal
109
Output_ShortCut
Output short circuit
Check if there is a short circuit at
loads.
110
Output_OverLoad
Output over load
Reduce the loads.
111
CoolSys_Err
Cooling system is abnormal
Checking if fan is working
properly.
112
U_BAT_Low_Deep
Battery is severely under
voltage
Connect to a valid grid or
generator. Restart the inverter
and charge the battery.
114
Instant_OC_Soft
Instantaneous over current
Check if there is a short circuit at
loads.
115
EPO
Emergency stop
Check the EPO Dry Input.
116
Rly_Err
Relay is abnormal
Restart the inverter. Contact your
installer if it still exists.