Kinergier Pro User Manual
35
AGS Logic Set Diagram
>AGS Logic Set
CHG Start Ubat
11.5V
CHG Stop Ubat
13.5V
Load Start Delay
5s
Load Stop Delay
30s
Load Start Power
80% (4800W)
Load Stop Power
50% (3000W)
Time Window From
00:00
Time Window To
23:59
CHG Stop Float
1- Enable
CHG Start Delay
30s
CHG Stop Delay
180s
Load AGS Logic
1- Enable
This mode is not
applicable to TBB
SUPER-L lithium
battery.
>AGS Logic Set
CHG Start SOC
30%
CHG Stop SOC
50%
Load Start Delay
5s
Load Stop Delay
30s
Load Start Power
80% (4800W)
Load Stop Power
50% (3000W)
Time Window From
00:00
Time Window To
23:59
CHG Start Delay
30s
CHG Stop Delay
180s
Load AGS Logic
1- Enable
This mode is
applicable to TBB
SUPER-L lithium
battery.
5.6.4 ACout2 Logic
Item
Setting range
Description
ACout2 Logic
-->Logic Mode
0-Default
1- Ubat / SOC Ctrl
2-Time Ctrl
3-PV_INV Ctrl
0-Default: ACout2 relay is turned on only when it is powered
by the grid.
1-Ubat Ctrl: Control ACout2 relay according to battery
voltage.
1-SOC Ctrl: Control ACout2 relay according to battery SOC.
2-Time Ctrl: Timing control on the ACout 2. .
3-PV_INV Ctrl: There is such option when AC couple mode
has been selected. After that option is set, the oversized PV
inverter can be connected to AC Output 2 to improve the AC
Coupled PV System applicability. The capacity of PV
inverter connected on the AC output 2 should not be larger
than the capacity of the battery inverter.