background image

11

APX-03 Keypad/Proximity Reader - Troubleshooting Guide

For Technical Support call 01704-502815. Monday to Thursday 8.30am - 5pm, Friday 8.30am - 4pm

Fault / Problem

Reason / Action required

Power light is not illuminated

Check input voltage is 12v DC (+/- 10%) at RED & BLACK wires.
Make sure Positive is connected to RED & Negative connected to  BLACK.

Check the Power unit is 12v DC Regulated with Minimum 1 Amp load.

Power light is permanently illuminated

This is normal and shows the Keypad is in standby mode.

Electronic Lock is not unlocking

Check the YELLOW wire is linked to RED or Positive output of PSU.

Check the voltage at the lock connections is 11-13v DC when the Relay
activates.

Check the correct colour wire is used to suit the lock function - see wiring
detail on page 2 (Fig 1 or 2).

Check Current draw of lock is less than 1amp. A Lock that has a current

draw of 1amp or over should be connected as wiring detail on page 3 Fig.3.

Electronic Lock is permanently Unlocked

Check the Exit button Connections are COM & N/O and check that the
Button is not stuck or jammed.

If no Exit Button is fitted check the BLUE & WHITE wires are not shorted out.

Check the correct colour wire is used to suit the lock function see wiring
detail on page 2 (Fig.1 or 2).

If an Emergency Call point is fitted check if it has been activated and reset.

Bell button does not activate the Bell/Sounder

Check the ORANGE wire is linked to RED or Positive.

Check the voltage at the Bell connections is 11-13v DC when the Relay
activates.

Re-program the Door Bell ringing time (see page 7).

Master Fob does not work after Initial Power up

Make sure you have entered "FUN - 2 - EN" before you presented the
Master Fob.

If after entering "FUN-2-EN" the error indicator flashes when the Master Fob
is presented this shows it is not programmed.

You will need to follow the Adding a New Master Fob instructions on page 8.

Lock does not open when I use my 4 Digit code

Make sure you press "CLR" before the 4 Digit code and "EN" after the
code.  (Note: The OK indicator should flash after

"

CLR" is pressed)

If the OK indicator does not flash after "CLR" is pressed it means a 4 Digit
code has not been programmed. Re-Enter the 4 digit code as per page 4.

Check the lock is wired correctly as per wiring detail on page 2 (Fig.1 or 2).

Lock does not open when I use my Fob

If the ERROR indicator and a low bleep sounds the Fob is not programmed,
Delete the Group of Fobs as per page 6 then Re-Program as per page 5.

If the Fob still won't work after the above it may have been deleted as a
single fob. Restore the deleted Fob as shown on page 7.

If the Fob is presented and neither the ERROR or OK indicator responds
the Fob's memory chip may be corrupted. Replace with a new Fob.

Check the lock is wired correctly as per wiring detail on page 2 (Fig.1 or 2).

The ERROR indicator came on during programming and

This means the wrong information has been entered.

now the POWER indicator is flashing

The Keypad has returned to the start of programming so you will need to

Re-Enter the Function code and all the information again.

I have 2 Keypads close together and they are not working

If the Keypads are close together they will cause interference which
prevents them from operating correctly. Power down both units and move

the keypads apart so there is a gap of at least 50cm(20") between them.

I have lost my Master Fob, how do I program keypad

If you loose the Master Fob the next lowest fob will need to be programmed as

the new Master Fob (see Adding a New Master Fob instructions on page 8.

The Keypad will not respond to Codes or Fobs

Power down the keypad and leave for 3 minutes then re-apply the power
and try the Codes or Fobs again.

If the keypad does not respond again check the Capacitor is fitted to the lock

 connections and replace if damaged. Power down again as above.

If you experience any problem or fault which is not resolved after reading the above contact Technical Support

Содержание APX-03

Страница 1: ...Fob and 4 Digit Group Code Mode 3 User Fob Group code Deleting a Single Fob Deleting a Group of Fobs Mode 2 3 Page 7 Restoring a Deleted Fob Changing Lock open Time Bell ringing time Changing the Mas...

Страница 2: ...on Keypad must be fixed to a flat and level surface The recommended fixing height is 1 1 5 metres from the floor If fixing more than 1 keypad ensure there is a gap of at least 50cm 20 to avoid interfe...

Страница 3: ...tail for Electric Release including Exit Button Link the Yellow wire to the Red wire Com N O Exit Button OK OK 1 1 2 2 3 3 FUN FUN 4 4 5 5 6 6 7 7 8 8 9 9 CLR CLR 0 0 EN MENU MENU F U S E N E L O P O...

Страница 4: ...nge and Grey wires are not used Magnetic Locks 12v DC Com N C Emergency Call Point Volt Free Relay Note Linking wiring from one magnet to the other will affect Holding force Note This wiring method ca...

Страница 5: ...of the Keypad as this will not allow the unit to be programmed correctly If the wrong information is entered the Error indicator will flash once along with a low tone bleep then the keypad will retur...

Страница 6: ...Bleep and OK indicator flashes once To Add a Group of Fobs by Fob No Enter into Programming mode as shown on page 4 Example Indication 1 2 Enter Function code 31 then EN FUN 31 EN OK indicator flashe...

Страница 7: ...ode entry Note To Delete a Group code follow the above programming but enter 0000 instead of the Group code When a Group code is deleted the Fobs will revert to Fob only Mode 2 operation Fob Code Oper...

Страница 8: ...and Power indicator flashes 6 Exit Programming Mode FUN 2 EN Long Bleep and OK indicator flashes once To Change Lock open time Note The number of seconds must be entered as 3 digits I E 5 Seconds 005...

Страница 9: ...r Adding a Master Fob when original Master Fob is Lost To Program a new Master Fob when the original has been lost you will need to remove the Front Cover of the Keypad and look for a label in the top...

Страница 10: ...FIRST FOB No LAST FOB No GROUP 01 GROUP 11 GROUP 02 GROUP 12 GROUP 03 GROUP 13 GROUP 04 GROUP 14 GROUP 05 GROUP 15 GROUP 06 GROUP 16 GROUP 07 GROUP 17 GROUP 08 GROUP 18 GROUP 09 GROUP 19 GROUP 10 GROU...

Страница 11: ...10 FOB No FOB No NAME FOB NUMBER NAME LIST CONT D NAME Photocopy this sheet if required...

Страница 12: ...page 8 Lock does not open when I use my 4 Digit code Make sure you press CLR before the 4 Digit code and EN after the code Note The OK indicator should flash after CLR is pressed If the OK indicator...

Отзывы: