©Copyright Task Force Tips, Inc. 2011-2012
LIA-520 April 25, 2011 Rev01
4
3.0 GENERAL INFORMATION
The Hydrant Master is a lightweight, low friction-loss hydrant valve that can be used in many water distribution applications. The
valve is powered by (4) AA batteries, pressure activated, and equipped with a power-save mode. A handheld controller with
pressure display and valve position feedback controls the valve up to 1200 feet (366 m) away. Both the valve and handheld are
equipped with backlighting for use in low-light situations. The valve opens and closes with a sliding plug which is compliant with
NFPA 1965 slow close requirements. The valve’s position is controlled by operating a control valve which can be moved manually,
operated electronically from push buttons on the valve, or by wireless remote control.
3.1 VALVE SPECIFICATIONS
Main LDH Waterway size (at valve seat): 4.5” (114 mm)
Meets NFPA 1965 3.3.11.3 Slow-Operating Valve requirement.
Minimum Operating Pressure: 5 psi (0.7 Bar) NOT FOR SUCTION USE.
Maximum Operating Pressure: 300 psi (20 bar)
Hydrostatic Proof Test Pressure: 900 psi (62 bar)
Temperature Rating*: -25°F to 135°F (-32°C to 57°C)
Batteries: 4 AA batteries, Lithium recommended
Expected valve battery life: 140 hours lithium, 100 hours alkaline
*For temperatures below 32°F (0°C), valves must be drained after use to avoid damage. See section 3.5 LOW TEMPERATURE
USE
Environmental Rating: All components designed to meet minimum rating of NEMA 4 (IP65).
3.2 WIRELESS HANDHELD REMOTE CONTROL SPECIFICATIONS
Batteries: 4 AA batteries, Lithium recommended
Expected handheld remote control battery life: 55 hours lithium, 40 hours alkaline
Specifi cations
900 MHz
2.4 GHz
Transmitting Power
100mW
10mW
Operating Range (Line of sight)
1200 ft (366m)
600 ft (183m)
Operating Frequency
900 MHz (902-928 MHz)
2.4GHz (2.410-2.470 GHz)
Agency Approvals
900 MHz
2.4 GHz
FCC
MCQ-XBEEXSC
OUR-XBEEPRO
Industry Canada (IC)
1846A-XBEEXSC
4214A XBEEPRO
Europe N/A ETSI
N/A
ETSI
Finished Good # AU-RU-900 Contains FCC ID: MCQ-XBEEXSC The enclosed device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (i.) this device may not cause harmful interference and (ii.) this device must
accept any interference received, including interference that may cause undesired operation.
Finished Good # AU-RF-2400 Contains FCC ID: OUR-XBEEPRO The enclosed device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (i.) this device may not cause harmful interference and (ii.) this device must
accept any interference received, including interference that may cause undesired operation.
3.3 CORROSION
Most hose couplings are attached using polymer bearing rings which provide electrical insulation to help galvanic corrosion.
The parts are hard anodized, and powder coated to help prevent corrosion. The effects of corrosion can be minimized by good
maintenance practice. See section
3.12 AIR FLUSH PORT & 6.0 MAINTENANCE
.
3.4 USE WITH SALT WATER
Use with salt water is permissible provided valve is thoroughly cleaned with fresh water after each use. The service life of the valve
may be shortened due to the effects of corrosion and is not covered under warranty.
3.5 LOW TEMPERATURE USE
The valve is designed with self-draining waterways. In extreme freezing conditions, extra precautions should be taken to ensure
control waterways remain free from ice. Residual water should be cleared from the valve after each use. See section
3.12 AIR
FLUSH PORT.