©Copyright Task Force Tips, LLC 2002 - 2018
LIA-200 March 20, 2018 Rev19
5
3.1 SPECIFICATIONS
MODEL
BALL INTAKE
VALVE
JUMBO INTAKE
VALVE
BALL INTAKE VALVE
RC
JUMBO INTAKE VALVE
RC
Waterway Size
3.65” (93mm)
5.25” (133mm)
3.65” (93mm)
5.25” (133mm)
Max Pressure
300 psi (20 bar)
250 psi (17 bar)
300 psi (20 bar)
250 psi (17 bar)
Min Pressure
Full Vacuum
Full Vacuum
Full Vacuum
Full Vacuum
Opening/Closing Speed
6 sec
6 sec
Voltage - Auto Sense
12 or 24volt DC
12 or 24volt DC
Motor Current
(RC Only)
Nominal
Limit
@ 12 VDC @ 24 VDC @ 12 VDC @ 24 VDC
3 amp
1.5 amp
12 amp
6 amp
Recommended Fuse or Circuit Breaker Size
15 amp@12 Volt
7.5 amp @ 24 Volt
Temperature Rating*
-25°F to 135°F (-32°C to 57°C)
*For temperatures below 32°F(0°C), valves must be drained after use to avoid damage. See section 2.0 SAFETY.
Environmental Rating
All components designed to meet minimum rating of NEMA 4 (IP65)
3.2 CORROSION
Aluminum parts are hard anodized. All castings are then powder coated inside and out to help prevent corrosion. Hose couplings are
attached using polymer bearing rings which provide electrical insulation to help prevent galvanic corrosion. The effects of corrosion
can be minimized by good maintenance practice. See section 9.0 MAINTENANCE.
3.3 USE WITH SALT WATER
Use with salt water is permissible provided valve is thoroughly cleaned with fresh water after each use. The service life of the valve
may be shortened due to the effects of corrosion and is not covered under warranty.
4.0 INSTALLATION
4.1 MOUNTING ON TRUCK
Screw the large coupling to the pump inlet manifold. The valve position indicator should be clearly visible, but need not be level.
4.2 ENCLOSURE MOUNTING
Select proper location for display. A full size template is shown in section 12.0.
4.3 ELECTRIC INSTALLATION AND WIRING
Red (+) and black (-) wires must be connected to a 12 or 24 VDC protected circuit from the truck’s power distribution center. Figure
4.3 shows the control connections.
MUL
TIPLE OPERA
TOR ST
ATIONS MA
Y BE INST
ALLED.
ALL
COMMUNICA
TION P
AIRS (BLUE & WHITE)
AND POWER
PAIRS (RED & BLACK) MUST
BE CONNECTED IN
TERMINAL
BOX OR
ANOTHER INTERF
ACE BOX.
INSTALLER
SUPPLIED
POWER CABLE
INTERFACE BOX
(OPTIONAL)
NOTE
:
CABLE IS GEL FILLED TO PREVENT MOISTURE WICKING INTO
ENCLOSURE. GEL IS NON-HAZARDOUS AND SHOULD BE
WIPED OFF CONDUCTORS WITH RAG.
RED
RED
BLACK
BLACK
BLUE
BLUE
WHITE
WHITE
RED
BLACK
TYPICAL TERMINAL BOX
CONNECTIONS
BLUE
WHITE
BIV OPERATOR
STATION
30 FT (9M) MAXIMUM
AB1ST-NX-RC
BALL INTAKE VALVE RC
BALL INTAKE VALVE
DUST CAP
PLUG
NOTE
:
TO AVOID EXCESSIVE VOLTAGE DROP AT VALVE MOTOR, DO NOT
LENGTHEN FACTORY SUPPLIED RECEPTACLE CABLE. POWER CABLE
SELECTION IS CRITICAL. VOLTAGE SUPPLIED TO VALVE MOTOR BOARD
SHOULD NOT FALL BELOW 10 VOLTS WHEN VALVE IS IN OPERATION.
INSTALLER SUPPLIED
TERMINAL BOX OR OPTIONAL
INTERFACE BOX CAN BE USED
ELECTRIC MOTOR
MANUAL OVERRIDE
HANDWHEEL
RECEPTACLE
Figure 4.3
WARNING
The electric motor and other components are ignition sources. The electric BIV should be operated only
in areas where there is adequate ventilation and no hazard of flammable vapor buildup.