NORMAL INSTALLATION STEPS
1. PROVIDE ADEQUATE GAS SUPPLY
This range is designed to operate on natural gas at 4" of
manifold pressure or on LP gas at 10" of manifold pressure.
It is shipped from the factory set for natural gas. If it is to be
used with LP gas, adjustments described on page 5 must be
made.
A convertible pressure regulator is connected in series with
the manifold of the range and must remain in series with
the supply line regardless of whether natural or LP gas is be-
ing used.
FOR PROPER OPERATION, THE MAXIMUM INLET PRESSURE
TO THE REGULATOR MUST BE NO MORE THAN 14" OF
WATER COLUMN PRESSURE.
For checking the regulator, the inlet pressure must be at
least 1" water column pressure greater than the regulator
manifold outlet setting. If the regulator is set for 4" of mani-
fold pressure, the inlet pressure must be at least 5". If the
regulator is set for 10", the inlet pressure must be at least
11".
The gas supply line into the range should be a 1/2" or
3/4" I.D. flexible metal appliance connector five feet in
length.
2. SEAL THE OPENINGS
Seal any openings in the wall behind the range and in the
floor under the range when hookups are completed.
3. CONNECT THE RANGE TO GAS
Refer to figures 1 to 4 for recommended connections.
1.
Install a manual shut-off valve
in the gas line in an
easily accessible location outside of the range. Be sure you
know how and where to shut-off the gas supply to the
range.
2. Install 1/2" flare union adaptor supplied with the con-
nector, to the 1/2" NPT internal thread on pressure regula-
tor.
3. Because solid pipe restricts moving the range, we re-
commended use of A.G.A. design certified flexible metal
appliance connector. Connect flexible appliance connector
to flare union.
4. Move range into approximate position and connect flex-
ible appliance connector to gas supply line with proper flare
union adaptor. The adaptor supplied with the flexible con-
nector must be used.
5.
Check for leaks.
Turn the gas supply on to the range
and use a liquid leak detector at all joints and connections
to check for leaks in the system.
SHUT-OFF FITTING
1/2" CLOSE NIPPLE
FLEXIBLE CONNECTOR
RECOMMENDED SHUT-OFF LOCATION
6 3/8"
1/2" NIPPLE
UNION
FLEXIBLE CONNECTOR HOOKUP
Figure 3
Figure 2
Figure 1
SOLID PIPE HOOKUP
32
7
/
8
" ±
1
/
4
"
3-WIRE POLARIZED
120V. OUTLET
GAS SUPPLY
PIPE
3"
25"
36"
36
1
/
4
"
6
3
/
4
"
3
CAUTION:
DO NOT USE A FLAME TO CHECK
FOR GAS LEAKS.
20"
OR LOWER
FLARE UNION
ADAPTOR
FLEXIBLE
APPLIANCE
CONNECTOR
PRESSURE
REGULATOR
GAS CONNECTION FOR ELECTRIC IGNITION MODELS
(a)
Disconnect this range and its individual shut-off
valve
from the gas supply piping system during any pres-
sure testing of that system at test pressures greater than
14" of water column pressure (approx. 1/2" psig.).
(b) The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply pip-
ing system at test pressures equal to or less than 14" of
water column pressure (approx. 1/2" psig.).