TANGRA HP 30 Скачать руководство пользователя страница 18

 

User manual  TANGRA HP30 - Rev. 04 - 2014-03-28      

 

 

   

18 

8.3  Set the capacity of the boiler: 

The capacity of the boiler depends on the quality and the quantity of the fuel supplied in the 
burner, measured in kg/h. The controller allows 5 levels – 1 (minimum capacity), 2.3.4 and 
AUTO (maximum capacity with automatic modulation). 

Set of the maximum capacity (AUTO level): 

  From menu Power choose Auto; 

  Remove the plug of the main auger of the burner; 

  Press and hold the button on/off, until on the display is On; 

  Wait minimum 60 s.; 

  Place a plastic bag at the end of the flexible connection; 

  Take out the flame sensor; 

  Connect the plug of the main auger to the burner. After 60 s the main auger will turn on; 

  Measure the quantity of pellets, passed through the main auger for 6 min. This quantity, 

multiplied by 10 gives the amount of fuel in kg/h. 

  Press and hold on/off button, until the display shown Off; 

Return the flame sensor. After 60-120 s the boiler will terminate loop of self-cleaning of 
the burner; 

  Connect the flexible connection for pellets to the burner. 

 
If you want to change the capacity  in Auto mode (highest capacity), enter in menu Setup, level 
Parameters,  change  parameter  18,  in  proportion  with  what  we  want  to  achieve  and  repeat,  to 
establish the capacity.  
 

 
Use  the  same  procedure  to  set  level  1  (minimum  capacity)  by  choosing  from  the  Menu 
parameter 10. 

The rest of the capacity levels (2,3,4) will be calculated automatically by the controller. 

We do not recommend capacity under 15kW. 

Note:  The correct choice of boiler capacity is of a great importance for the trouble-free 
and  flawless work of the unit. Before setting the maximum and minimum capacities, 

please check what is the total necessary capacity of the building (according to the project). 
Please, pay attention if the boiler will be used only for heating or for heating and domestic hot 
water.  

 

It is forbidden the value of the lower capacity (level 1)to be lower than the necessary 
capacity of the building.  Otherwise, the boiler will work without pauses and will not 
commit a self cleaning cycles which could cause blocking or stopping of the burner.  

 

Heating capacity, kW 

12.5 

15 

17.5 

20 

22.5 

25 

27.5 

30 

Fuel, kg/h 

2.6 

3.1 

3.7 

4.1 

4.7 

5.2 

5.7 

6.2 

Содержание HP 30

Страница 1: ...Manufactured in accordance with standard EN 303 5 Rev 04 2014 03 28 Installation and operation manual for pellet boiler TANGRA HP 30...

Страница 2: ...User manual TANGRA HP30 Rev 04 2014 03 28 2...

Страница 3: ...irements to the pellets 17 8 Commissioning 17 8 1 Filling the installation 17 8 2 Initial filling of the auger 17 8 3 Set the capacity of the boiler 18 8 4 Set the temperature in the boiler 19 8 5 Ini...

Страница 4: ...User manual TANGRA HP30 Rev 04 2014 03 28 4...

Страница 5: ...User manual TANGRA HP30 Rev 04 2014 03 28 5...

Страница 6: ...g or cleaning the unit all safety rules should be strictly observed The use of personal protective equipment is required Changes in the construction of the unit and all its components without consulti...

Страница 7: ...with hot parts of the boiler or chimney could lead to seriouse burns and injuries Mandatory use of protective gloves Do not open the burning chamber s door during operation This could lead to injurie...

Страница 8: ...Turn on off the boiler from the main supply to the boiler is done with the key that is located on the right of the control panel This key is single pola and provides on off only of the phase conducto...

Страница 9: ...tion operation and maintenance Repairs from the buyer himself or an unauthorized maintenance company Changes in the construction of the unit Units which capacity is not correctly selected Damages caus...

Страница 10: ...UM DRAUGHT IN THE CHIMNEY Pa 20 OVERALL DIMENSIONS OF PELLET BOILER B L H mm 710 890 1600 OVERALL DIMENSIONS OF PELLET STORAGE TANK B L H mm 710 890 1600 TOTAL WEIGHT kg 320 MAXIMAL PRESSURE OF WATER...

Страница 11: ...ts of the boiler TANGRA HP 30 fig 1 N Name 1 Connection to the chimney system 2 Connections to the heating system 3 Controller 4 Auger for automatic supply of the burner with fuel 5 Pellet storage tan...

Страница 12: ...d prior to transport All unit components should be inspected for transport damages immediately upon delivery with annotations made on the delivery slip as appropriate Damages caused during transport w...

Страница 13: ...ct operation of the boiler Room temperature from 5 C to 40 C Relative humidity up to 90 at 20 C decreasing to 50 at 40 C Degree of environmental pollution 2 It is forbidden to install the boiler in li...

Страница 14: ...fan coil units closed or opened type Mixing unit should be installed in order to decrease the temperature of the water after the boiler It is totally forbidden to install stop and control valves betwe...

Страница 15: ...he boiler body and is leveled in a way similar to the boiler body Both units shall be leveled one to another and to fit fig 6 Both parts are connected with 6 bolts M8 two based in the main plate and 4...

Страница 16: ...th connector which supply the compressor and the auger according to fig 5 Burner bottom view 5 It is forbidden to install the boiler in the technical room on the transport pallet The pallet must be re...

Страница 17: ...of pellets 8 Commissioning 8 1 Filling the installation Filling the installation filling with fuel and check the integrity of the unit After the installation of the boiler and its connection to the h...

Страница 18: ...exible connection for pellets to the burner If you want to change the capacity in Auto mode highest capacity enter in menu Setup level Parameters change parameter 18 in proportion with what we want to...

Страница 19: ...means that the boiler is in ignition mode When appeared a stable flame 3 10min the boiler turn into working mode and the lamp light up permanently The boiler works at maximum capacity until it reaches...

Страница 20: ...last page 10 Decommissioning When decommissioning a unit the following activities are to be carried out When dismantling a unit all components which are under voltage must be switched off The unit mu...

Страница 21: ...please contact the your installer or the manufacturer find contacts on the last page 11 2 Smell of flue gases Flue gases could cause fatal poisoning In case you smell a flue gases Turn off the power s...

Страница 22: ...User manual TANGRA HP30 Rev 04 2014 03 28 22 12 Appendix 12 1 Wiring diagram...

Страница 23: ...can affect the operation of the unit and it is not recommended by the manufacturer Switching on off the boiler is done by holding the On OFF button This button ensures functional start up of the boile...

Страница 24: ...to the Table on next page for descriptions of the buttons It is possible to activate keyboard sound signal The following sound alarms are available Short high tone sounds when navigating the menu and...

Страница 25: ...User manual TANGRA HP30 Rev 04 2014 03 28 25 13 2 Schemes of the main menu...

Страница 26: ...User manual TANGRA HP30 Rev 04 2014 03 28 26 13 3 Description of the functions...

Страница 27: ...User manual TANGRA HP30 Rev 04 2014 03 28 27...

Страница 28: ...4 03 28 28 13 4 Service menu of the boiler Possible errors 001 Keyboard error E004 Motherboard communication error E108 security switch error E110 NTC1 error temperature sensor E111 TC1 error temperat...

Страница 29: ...rent by reaching of which the controller starts fire up Example if 1 65 and parameter 50 10 the boiler will restart at 1 55 o C 5 20 5 51 Tgiven required water temperature in the boiler When Tgiven is...

Страница 30: ...and blow cleaning started s 0 120 30 82 Minimal air quantity entering at the burner under which alarm is activated stuffed chimney fan failure etc 1 100 20 83 Time delay before triggering pressure er...

Страница 31: ...User manual TANGRA HP30 Rev 04 2014 03 28 31...

Страница 32: ...User manual TANGRA HP30 Rev 04 2014 03 28 32...

Отзывы: