Area of Rescue Command Unit
Installation Guide
Model AOR-5 / Model AOR-10
Page
21
of
23
Rev. 4/13/2022
Copyright 2022 Talk-A-Phone, LLC
• 7530 North Natchez Avenue • Niles, Illinois 60714 • Phone 773.539.1100 • [email protected] • www.talkaphone.com.
All prices and specifications are subject to change without notice. Talk-A-Phone, Talkaphone, bAlert, Scream Alert, WEBS, and WEBS Contact are registered trademarks of
Talk-A-Phone, LLC. All rights reserved. All other trademarks mentioned in this document or website are the property of their respective owners and does not imply or indicate
any approval, endorsement, sponsorship, or affiliation with such owners unless such approval, endorsement, sponsorship, or affiliation is expressly indicated.
5.
Primary Power Loss:
When the Command Unit loses primary power and begins to run on battery backup, the
POWER
LED will disengage or turn off on the Command Unit panel.
The
POWER
LED will illuminate once the primary power has been restored.
X.
System Maintenance
NFPA 72 requires that area of refuge two-way communication systems be
inspected, tested, and
maintained
on an
annual basis
. NFPA 72 specifies the method required as
“verify location and
condition”.
As such, the following guidelines are highly recommended:
•
An annual inspection and testing be scheduled as part of the facility/building preventative
maintenance schedule
•
Each AOR-CSE Station should be inspected and tested.
•
The Command Unit should be inspected and tested.
•
The Sub-Command Unit(s) should be inspected and tested.
•
Verify the condition of the backup battery and replace if necessary.