Ultraf – Installation and Operation Guide| Revision B | Updated 18/12/17
12
Pulse Output
Ultraf Pulse Output sends a signal each time a pre-determined amount of water passes. The meter units and the
amount (volume) are configured through the Raphael Ultraf mobile application
(see Pulse Output Control on page
.
Pulse output is ideal when flow indication is delivered to:
■
Irrigation controller
■
Flow controller
■
Water flow logging
Output specifications
■
Pulse type –
“Open Collector” N CH. Mosfet
■
Maximum Current –
100 mA
■
Maximum voltage –
18VDC
■
Pulse width –
1 second (+/- 0.1)
Wiring instructions
1. Connect the Ultraf
red
wire to
input
terminal on the reading device.
2. Connect the Ultraf
black
wire to the
common
terminal on the reading device.
3. Connect the Ultraf
shield
wire to the
GND
terminal on the reading device.
Typical wiring diagram
Red
Red
Black
Black
Ultraf
Input
Input
Common
Common
Reading Device
Ultra F
Shield
Shield
GND
GND