CP-600DC-ID Guide
84744 Rev 2 Sept 2015
GENERAL
The CP-600DC-ID is a split core CT meant for
operation with the Megger Power Quality Line
of Instruments. This current clamp will measure
both AC and DC current.
This CT is NOT
powered by the unit.
This CT requires a 9V
battery to operate.
NOTE:
If using this CT with a PA-9 series
power quality analyzer the PA-9
current full scale value MUST be
set to 1000.
SAFETY and SYMBOLS
WEEE
The crossed out wheeled bin placed
on Megger products is a reminder
not to dispose of the product at the
end of its life with general waste.
Megger
is registered in the UK as a
Producer of Electrical and
Electronic Equipment. The
Registration No is WEE/DJ2235XR.
Equipment complies with current
EU directives.
Application around or removal from
hazardous live conductors is
permitted.
Equipment protected throughout by
double insulation.
G
CAUTION
is defined as a condition
or practice which could result in
damage to or destruction of the
equipment or apparatus under test.
F
WARNING is defined as a condition
or practice which could result in
personal injury or loss of life.
Safety warnings are precautions that must be
read and understood before the instrument is
used. They must be observed during use.
Do not leave the instrument connected to the
system under test when not in use.
Always use extreme caution when connecting
the instrument around bare conductors, under
fault conditions, high voltage or currents may
be present and may pose a shock hazard.
Personal protective equipment (PPE) must be
used during the installation and removal of this
instrument from hazardous live connectors.
Do not touch circuit connections or any metal
that is exposed due to damaged insulation.
Do not use the instrument or connect it to any
external system if it shows any visible signs of
damage, malfunction or if it has been stored in
unfavorable conditions.
Always inspect the instrument prior to use.
Replace any defective parts or return the
instrument to an authorized center for repair.
Do not use the instrument or connect it to any
external system if the enclosure is open or any
parts of the enclosure are missing.
Only use specified batteries as described by
this document, if applicable.
The instrument shall not be used if any parts
are damaged.
Always connect the probe to the instrument
prior to connecting to the source.
This instrument is not intrinsically safe and
must not be used in hazardous atmospheres.
If this equipment is used in the manner not
specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
Working / Common Mode Voltage: 600Vrms
Current Range
1 to 600A
Scale
1mV / Amp
Load Impedance
>100K
Ω
/ 100pF
Bandwidth:
DC to10KHz @ -3dB
Accuracy:
400A Range
1 to 100A = 1.5% of reading
+/- 1A
100 to 400A = 2% reading
Accuracy
600Adc Range
400 to 600A (DC ONLY) =
2.5% of reading
Phase Shift
1 to 200A
≤
2.5
°
200 to 400A
≤
2.0
°
Overload
2000Adc & 1000Aac
Continuous up to 1KHz
Power Source
9V Alkaline Batteries NEDA
1604A, IEC 6LR61 (120-HR
LIFE)
Jaw Opening
1.2 inches (31mm)
Dimensions
8.8x3.82x1.73”
(224x97x44mm)
Weight
15oz (440g)
Operating
Temperature
-10 – 55C
Storage
Temperature
-40 – 80C
Humidity
10-35C 90% +/- 5% NC
40-55C 70% +/- 5% NC
IEC61010-2-032: 2012
EN50081-1 Class B
EN50082-2 Electrostatic Discharge; IEC61000-4-2
Radiated Field IEC61000-4-3
Fast Transient IEC61000-4-4
Magnetic Field 50/60Hz IEC61000-4-8
600V CAT III, Pollution Category 2
*Reference conditions: 23°C ±3°K, 20 to 75% RH, 48 to
65 Hz, external magnetic field < 40 A/m, no DC
component, no external current carrying conductor, test
sample centered. Load impedance 1M
Ω
.