Ultraf – Installation and Operation Guide| Revision B | Updated 18/12/17
10
Recommended Installation Examples
The following examples provide recommendations for Ultraf optimal performance.
A minimum of two pipe diameters after elbows (90°).
A minimum of two pipe diameters after an isolating
valve.
A minimum of ten pipe diameters after pumps.
A minimum of two pipe diameters after strainers.
A minimum two pipe diameters after elbows (90°) in
vertical installations.
Flo
w Dir
ection
2 DN
10 DN
2 DN
2 DN
Fl
ow Dir
ection
Flo
w Dir
ection
Flo
w Dir
ection
Flo
w Dir
ection
2 DN