This sensor is designed to detect ultraviolet rays contained in
flames, and to issue a signal.
This unit is neither fire detector nor heat detector nor smoke
detector.
TAKEX is not responsible for damage, injury or losses by fire,
accident, calamity, Acts of God (including inductive surge by
lightning), abuse, misuse, abnormal usage, faulty installation or
improper maintenance.
◎
Carefully select the installation site and set up the sensor to avoid dead spots.
◎
Do not install in the following places.
Product classification
●
When an strong impact is given to the sensor, it may cause
damage, malfunction or less performance.
Do not handle in a rough manner.
●
Intense flames such as gas explosion's may damage the
sensor, and there may be no detection.
Others
This sensor detects ultraviolet rays contained in flames.
Therefore, this sensor may detect other sources of ultraviolet rays.
This sensor does not detect burning objects which are smoldering.
Objects to be detected
2
ATTENTION
3
DO'S AND DON'T'S
Do not install in a site
which is subject to direct or
reflecting sunlight and rain.
(This sensor is for indoor
use only)
Do not install in high
humid place such as a
bathroom.
Do not install in a site
where fire (flame) is usually
used such as a kitchen.
Do not install in front of the
object that intercepts light.
(including glass and trans-
parent resin etc.)
●
Do not install in a site where the temperature falls to less
than
+
14
°
F (
-
10
°
C) or rises more than
+
140
°
F (
+
60
°
C).
●
Do not install the sensor nearby the possible cause of false
alarm. (see section 2)
●
Do not give an impact to the sensor. it may cause damage,
malfunction and less performance to the sensor.
●
Do not put water on the sensor, or leave the sensor in a humid
place. it may cause malfunction.
●
Only type-AA Alkaline battery (2 pcs.) can be used.
Do not use manganese battery because of its short life.
●
When low battery alarm is initiated, exchange the battery
immediately. If not, the sensor may not work.
●
This sensor's alarm action is 10 sec. offdelay action.
By detecting a flame, the alarm will be initiated after the set
time of timer passed.
The alarm action is continued during the fire, and stopped 10
sec. later after the extinction.
(Alarm, LED, external output)
Possible cause of false alarm
Do not install the sensor nearby the followings.
Flames which can not be detected.
●
Halogen lamp
●
Electric discharging lamp such as mercury lamp
●
Electric sterilizer lamp
●
Spark from welding
●
Electric spark (caused by motor, pantograph)
●
Sunlight
●
Lightning discharge
●
High voltage electric field
●
All objects which emit ultraviolet rays
●
Flames through glass or transparent resin
●
Lit portion of cigarette
●
Burning charcoal or briquet
●
Electric stove
●
Smoldering object
●
●
●
●