3.

 

Operation & Dip Switch Settings:

 

 

General Operation:

 When any thermostat calls for heat,  

the appropriate circulating pump is energized, the red light goes on and the 

boiler end switch relay and AUX circulator relay(s) are energized. 

Expansion Connections: 

Set dip switch (#1) to MASTER on the switching relay 

that is designated as the priority zone control. Set all other daisy chained zone 

controls to EXPANSION.  Using thermostat wire (18-22 gauge) connect between 

terminals 1, 2, 3  on  the master  control  to  the  corresponding 1, 2,  3  on the 

expansion zone control(s). Zone controls may be daisy chained up to 20 Taco 

zoning panels using any combination of SR and ZVC controls (120 zones if all 

are 6 zone panels). 

Priority Operation: 

When the priority dip switch (#2) is set to ON and the priority 

zone (zone 1) is actuated, all other zones will stop operation until priority  zone 

is satisfied. When not switched to priority, all zones will operate independently. 

More adjustments are available when using the eLink mobile app. 

Priority Protection Operation:  

If the priority zone calls continuously for more 

than  one hour,  power  is returned to all the other zones, allowing each zone to 

function  independently.  Once the priority zone is satisfied, the control's auto-

reset is  activated, and the priority zone is again allowed to have priority for up to 

one hour starting from when it calls next. 

Primary  Pump  Operation: 

When  the  dip  switch  (#3)  is  set  to  OFF,  the  primary 

circulating pump output will energize when any zone calls for heat,  except  the 

priority  zone.  When  the  dip  switch  is  set  to  ON,  the  primary circulating pump 

output will energize when any zone calls for heat. 

Post Purge Operation: 

When the dip switch (#4)  is set to ON, the priority 

zone output will stay energized for 2 minutes after its thermostat or aquastat is 

satisfied, but not operate the boiler. More adjustments are available when using the eLink mobile 

app. 

Pump Exercise Operation: 

When the dip switch (#5) is set to ON, the solid  state  timer  cycles  all  the 

circulating  pumps  that  are  attached  to  the  Switching  Relay  t o   run for 30 seconds every 2 

weeks. More adjustments are available when using the eLink mobile app. 

Low Limit (ZC) Operation: 

When the dip switch (#6)  is set to ON and the boiler drops below the 

set low limit (terminal ZC connected to boiler), all zone circulating pumps will stop. When the boiler 

rises above the  set low limit, the zone circulating pumps are allowed to operate. 

AUX 1; ZR /Circulator Output: 

The AUX 1 output is energized when any zone calls for heat.        

More adjustments are available when using the eLink mobile app. 

AUX 2; Primary Circulator Output: 

The AUX 2 output follows dip switch setting # 3 listed above. 

More adjustments are available when using the eLink mobile app. 

SmartPlus

®

 Recirc Logic:

 

SmartPlus adds intelligence to your system by learning when hot water is 

used in the home. The pipe-mounted sensor records daily hot water usage patterns during the 

course of the week. Recorded data is used to automatically run the circulator at the same times the 

following week. So hot water is always available when it is needed. If usage pattern changes, the 

SmartPlus adjusts automatically.  

“Smart” Mode 

(default mode): the SmartPlus logic will run in Pulse mode as described below 

for the first 7 days of operation. During the first 7 days, the SmartPlus logic monitors and 

records the home's hot water usage pattern. For the following 7 days, the SmartPlus logic will 

use the preceding week's usage pattern to cycle the pump during the recorded hot water usage 

times. This process of recording and repeating is continuous, and automatically adjusts the 

pump "ON" times to match the house hold's usage pattern. 

“Pulse” Mode: 

When set to Pulse mode, the SmartPlus logic will cycle the circulator pump "ON" 

for 5 minutes, then “OFF” for 10 minutes to maintain hot water at all faucets and taps. It will 

repeat the cycle continuously.

 

More adjustments are available when using the eLink mobile 

app. 

When a sensor is connected to the Recirc sensor input, zone 2 output will now be designated for 

recirculation of DHW loop and activated based on DHW usage. 

 

 

Содержание SR506-5

Страница 1: ...o operate and deactivate zones 2 through 6 during a priority call this is ideal for when using an indirect water heater The SR506 5 includes timing options for Post Purge Pump Exercise and Priority Protection The SR506 5 includes an energy saving program that can adjust the temperature of a modulating condensing boiler or conventual On Off boiler to increase the comfort level and use less fuel wit...

Страница 2: ...g the FCC radio frequency exposure limits human proximity to the antenna shall not be less than 20 cm during normal operation and must not be co located or operating in conjunction with any other antenna or transmitter ISED Regulatory StatementsThis device complies with ISED Canada license exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interf...

Страница 3: ...al connectors for field wiring Low and live voltage wiring per code Location Do not mount to a surface that exceeds 104 F 40 C The unit must be only located in dry interior locations Use only copper conductor supply wire suitable for at least 105 C All circuits must have a common disconnect and be connected to the same pole of the disconnect Product is not suitable for installation in hazardous lo...

Страница 4: ... is set to ON the solid state timer cycles all the circulating pumps that are attached to the Switching Relay t o run for 30 seconds every 2 weeks More adjustments are available when using the eLink mobile app Low Limit ZC Operation When the dip switch 6 is set to ON and the boiler drops below the set low limit terminal ZC connected to boiler all zone circulating pumps will stop When the boiler ri...

Страница 5: ...ZR AUX 1 120 vac H Connect the Hot output to Hot power input on circulator or to ZR see below N Connect the Neutral output to Neutral power input on circulator G Connect ground wire to ground screws on base of zone control Circulator Output Primary AUX 2 120 vac H Connect the Hot output to Hot power input on circulator N Connect the Neutral output to Neutral power input on circulator G Connect gro...

Страница 6: ...Headers Mechanical Diagram Electrical Diagram Dip Switch Settings 1 OFF Master 2 ON Priority 3 OFF Primary Pump 4 OFF or ON Post Purge 5 OFF or ON Pump Exercise 6 OFF ZC Low Limit Conceptual Sketches Only refer to individual manufacture s installation instructions for additional d t il L l d h ll il ...

Страница 7: ...gram Electrical Diagram Dip Switch Settings 1 OFF Master 2 ON Priority 3 OFF Primary Pump 4 OFF or ON Post Purge 5 OFF or ON Pump Exercise 6 OFF ZC Low Limit Conceptual Sketches Only refer to individual manufacture s installation instructions for additional details Local codes h ll il ...

Страница 8: ...sion 1 ON Expansion 2 OFF Priority 3 OFF PrimaryPump 4 OFForON PostPurge 5 OFForON PumpExercise 6 OFF ZCLowLimit PA03 C High Low Temp Temperature Zones Indirect DHW Primary Secondary Mechanical Diagram Electrical Diagram Conceptual Sketches Only refer to individual manufacture s installation instructions for additional details Local codes shall prevail ...

Страница 9: ...urces of power may be connected to an oil boiler s aquastat control Beforeservicinganoilfiredboilermakesuretheserviceswitchisoff Thenconfirmthatasecondarysourceofpowerdoesnotexisttotheboiler s aquastatcontrol Failuretofixtheproblemcouldresultinboilerbeingactivatedwhenzonecallsforheat thatcouldresultinseriousinjuryordeath Conceptual Sketches Only refer to individual manufacture s installation instr...

Страница 10: ...pp is required to set type of reset control and parameters to operate See section 7 for more information on the Taco eLink mobile app Wiring of Reset Control Remove the inner cover as shown in section 10 page X of this manual to have access to wire Sensor Connections Boiler Sensor A boiler supply sensor is required for either indoor or outdoor reset Wire the supplied strap on sensor to the Boiler ...

Страница 11: ...ice to download the mobile app iOS Android OS Follow the app menu to configure advanced features that the Taco new zone controls have to offer including Different levels of access Zone naming Programmable output naming Alerts messages Post purge time delay adjustment Pump exercise time delay adjustment Priority protection time delay adjustment Indoor boiler reset Outdoor boiler reset SmartPlus DHW...

Страница 12: ...The eLink APP ...

Страница 13: ...The eLink APP ...

Страница 14: ...tor a 1000 ohm watt resistor has proven to work with most Problem No heat in a zone or room of building Solution LED diagnostic lights will help find a component that is not working properly The green LED should always be on indicating that power is connected and the solid state fuse is good When there is a call for heat the red LED will come on indicating power to the zone circulator This indicat...

Страница 15: ... 5 to 90 RH noncondensing Sensor Temperature Rating 58 F to 230 F 50 C to110 C DIP Switch Timing Settings Post Purge 30 seconds adjustable with mobile app Pump Exercise 30 seconds per 2 weeks of space heating inactivity adjustable with mobile app Thermostat Compatibility Compatible with most mechanical battery operated power stealing power robbing hardwired and Smart thermostats Temperature Sensor...

Страница 16: ...whetheraparticularsubstanceis suitableforusewithaTaco productorpart orfor anyapplicationrestrictions consulttheapplicable Taco instructionsheetsorcontactTacoat 401 942 8000 Taco reservestherightto providereplacement productsandpartswhicharesubstantiallysimi lar indesignandfunctionallyequivalenttothe defectiveproductorpart Taco reservestherightto makechangesindetailsofdesign construction or arrange...