iWorx® CSM1

6

 

502-045, Effective: July 25, 2013 

© 2013 Taco Electronic Solutions, Inc.

Mounting the Device

1.Select a mounting location. Enclosure mounting is recommended. 
2.Hold the controller on the panel you wish to mount it on. With a marker or pencil mark the mounting locations on 

the panel. 

3.Using a small drill bit pre-drill the mounting holes. 
4.Using two #6 pan head screws, mount the controller to the panel. 
5.Wire the controller (See Routing Cabling to the Device). 

Figure 1: Mounting Dimensions

Routing Cabling to the Device

Cabling used to connect the power source and cabling used to connect the FTT-10A network must remain 
separated within the control enclosure and wiring conduit.  

Содержание iWorx CSM1

Страница 1: ...stallation Guide 4 General 4 Static Electricity 4 FCC Compliance 4 Before Installing 5 About this Document 5 Inspecting the Equipment 5 What is Not Included with this Equipment 5 Equipment Location 5...

Страница 2: ...re measurement Outside air humidity measurement Supply water temperature measurement Inside humidity measurement Energy meter digital input for pulse counting Energy monitoring end of period digital i...

Страница 3: ...n information about the Chilled Beam Sensor Module including sequence of operation and configuration information iWorx LCI Application Guide Document No 505 002 Application Engineers Installers Servic...

Страница 4: ...connections in accordance with these instructions and in accordance with pertinent national and local electrical codes Use only copper conductors that are suitable for 167 F 75 C Static Electricity St...

Страница 5: ...d humidity within the ranges specified for this equipment The equipment must be installed within 500 feet of all input peripherals smoke detectors sensors etc that are con nected to the equipment Sele...

Страница 6: ...encil mark the mounting locations on the panel 3 Using a small drill bit pre drill the mounting holes 4 Using two 6 pan head screws mount the controller to the panel 5 Wire the controller See Routing...

Страница 7: ...risk of electrical shock and may increase the possibility of interference with radio TV reception For best performance connect the power supply common terminal T38 to the same external point as the g...

Страница 8: ...he adjacent common T4 The thermistor used must be 10K Precon Type III Chilled Supply Water Temperature CSWT To connect the Chilled Supply Water Temperature thermistor to the unit attach one wire from...

Страница 9: ...thermistor Energy Monitor End of Interval Normally open Dry contact 5 Volts DC Max Unit Enable Normally open closed when active Dry contact 5 Volts DC Max Recommended Sensor Wire Maximum Length 500 fe...

Страница 10: ...s of the controller s LEDs in the order they appear from left to right on the unit LED Indication Status Solid green when running and configured by an LCI networking Flashing green when running and NO...

Страница 11: ...firmware version number A complete description of difficulties encountered Problem Solution Controller is not running and Status LED is not illuminated No power to controller Verify the voltage on th...

Страница 12: ...red by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other app...

Отзывы: