Parameter table:
Code
Description
Factory setting
A
Water inlet temperature
Current data
b
Water outlet temperature
Current data
c
Ambient temperature
Current data
d
Temperature set
27 °C
E
Automatic defrost activation time
40 min
F
Maximum defrosting time
30 min
H
Set temperature difference for the restart
3 °C
J
Automatic restart
1
O
Frost protection - low air temperature
8 °C
P
Evaporator temperature for entry into defrost mode
-3 °C
U
Evaporator temperature to exit defrost mode
20 °C
t
Reserved - do not change
Reserved
6. Maintenance
ATTENTION:
Before performing any maintenance tasks, disconnect the electrical device from the
power source by pulling the plug out of the socket outlet.
Do not use aggressive solvents or cleaning agents.
Do not dispose of pool water containing chemicals (e.g. chlorine) on lawns or plants.
The evaporator on the back of the heat pump must be cleaned carefully with a ho over and a soft brush
attachment.
Note: All types of repairs must be carried out by qualified personnel.
Annual maintenance:
•
Carry out security checks.
•
Check the integrity of the electrical wiring.
•
Check the earth connections.
Your heat pump is designed to work even in rainy weather and is protected from frost by specially developed
anti-frost technology. However, it is not recommended to leave them outdoors for long periods (e.g. over
winter). After draining the pool, store the heat pump in a dry place for the winter.
Help in case of faults:
Code
Fault
Possible cause
Remedy
P1
Fault in the water inlet
temperature sensor
Sensor poorly connected
Reconnect sensor
Sensor defective
Replace sensor
Defective control panel
Replace control panel
P3
Fault in the evaporator
temperature sensor
Same causes as P1
Same causes as P1
P5
Fault of the external
temperature sensor
P7 Freeze protection
Protection is activated when the
ambient temperature is too low
No input is required
E3 Flow sensor fault
Not enough water in the heat
exchanger
Review the operation of your water circuit
Defective flow sensor
Replace flow sensor
Defective control panel
Replace control panel
E6
Negative pressure
protection
Insufficient refrigerant gas
Refill refrigerant gas
16