TAC 200 User’s Manual
2 General
2.1 Mounting
Type TAC 200 controller
The TAC 200 has a plastic enclosure with a transparent cover. Install the
controller in accordance with the enclosed instructions. Place the controller so
that you can easily adjust and read the display.
Cable entries for cables from sensors and actuators are provided for in the
mounting and terminal plate.
Type EGU outdoor sensor
Mount the sensor on an external wall facing north or northwest. The sensor
should be located about 3 m above the ground and the cable entry should be
oriented downwards.
Type EGWS/EGA water temperature sensors
Install the EGWS pipe sensor in the riser pipe 0.5-1 m downstream of the
shunt valve. If a clamp-on sensor is fitted, mount this on an uninsulated part of
the riser pipe. Carefully rub down the pipe so that the copper plate of the
sensor will make good contact.