TAC AB, Feb 2000
2:2
General
TAC 200 User’s Manual
Type EGF 1 or EGRL room temperature sensors
To ensure the best possible results, observe the following when installing the
room temperature sensor.
The sensor must be located in a room which is typical for the building.
The room must be sufficiently large so that no wide temperature variations will
occur due to local heat sources, such as machines or occupants.
The room must not be equipped with thermostatic valves.
Locate the room sensor so that its time constant will be as short as possible. To
achieve this:
– Mount the sensor on an inner wall made of lightweight building material,
such as wood or plasterboard. Avoid mounting it on a concrete wall.
– Mount the sensor in an open location to ensure good circulation of air
around it.
– Locate the sensor within 10 m from a radiator, but not directly above a
radiator. This is particularly important in rooms without mechanical
ventilation. The air velocities are then often low, which will cause a sluggish
response of the control system.
Type M44, M5, M15, M42 actuators
Installation instructions for actuators are supplied together with the actuator
and its its installation kit.