NOTE: If the communication settings have been changed they are activated upon exiting the 
Maintenance Mode - the device carries out a soft reset. Alternatively power cycle will activate 
the new communication settings.

Parameter Storage

The configuration parameters are stored in the non-volatile memory. When the changes are carried 
out via the display, the parameters are stored in the non-volatile memory when the controller returns 
to a normal display mode. If the changes are carried out over the network (Modbus), then "NonVol 
Update" flag is required to be forced on to save the changes. When configured via the display, when 
the parameters are stored after the timeout or exit button.

Modbus Registers 

The controller supports the following Modbus registers and function codes. The default 
communication speed is 9600 bps, 8 data bits, Parity None and 1 Stop Bit. The default Modbus Slave 
address is 1. The device Parity can be changed between Odd, None and Even. The baud rate is 
selectable between 9600, 19200, 38400, 57600 and 76800 bps.  The table shows the register offsets 
starting from 0 (0 Base) register address. For example, the Temperature is read from Modbus register 
100 using Function Code 04. Some Modbus masters will require one to be added to Modbus registers 
(i.e. 1 Base). In this case Function Code 04, register 101 needs to be entered. 

Version

Software Version

x.xx (Modbus/BACnet)

SYSTEM
Parameter Name

Description

Range

Register

Parameter Description

Data Type

Raw Data

Range

FUNCTION CODE 01 - READ COILS
FUNCTION CODE 05 - WRITE SINGLE COIL
FUNCTION CODE 15 - WRITE MULTIPLE COILS

100

Off Mode Override (last transition commands)

0..1

Off - On

101

ECO Mode Override (last transition commands)

0..1

Off - On

102

Show Frost Icon

0..1

Off - On

103

Boost Override (Override Boost Icon)

0..1

Off - On

FUNCTION CODE 02 - READ DISCRETE INPUTS (Add 10,000 for Modicon Addressing)

100

Digital Input Status

0..1

Off - On

101

Relay Output Status

0..1

Off - On

102

Time Clock Status (SRI-P70 Only)

0..1

Off - On

103

Light Switch Status

0..1

Off - On

104

A/C Switch Status

0..1

Off - On

105

OFF Mode Status

0..1

Off - On

106

Screen Lock Status

0..1

Off - On

107

Party Mode (Boost) Status

0..1

Off - On

108

ECO Mode Status

0..1

Off - On

109

Low Battery/Time Lost (SRI-P70 Only)

0..1

Off - On

110

Auto Fan Status (fan in auto mode)

0..1

Off - On

FUNCTION CODE 04 - READ INPUT REGISTERS  (Add 30,000 for Modicon Addressing)

100

Built-In Temperature Measurement

Signed 16

-400...3020

-40.0...150.0°C
(-40.0..302.0°F)

101

Resistive Input 1 Measurement

Signed 16

-400...3020

-40.0...150.0°C
(-40.0..302.0°F)

102

Resistive Input 2 Measurement

Signed 16

-400...3020

-40.0...150.0°C
(-40.0..302.0°F)

103

Current Calculated Setpoint (°C)

Signed 16

-400...3020

-40.0...150.0°C
(-40.0..302.0°F)

104

Interface Current Mode

Unsigned 16

0..3

0 = Comfort
1 = OFF
2 = Party (Boost) Mode

105

Relative Humidity Measurement (with RH 
option)

Unsigned 16

0..1000

0..100.0 %rH

106

Alarm State

Unsigned 16

0..256

Bit 0 - Internal NTC (1)
Bit 1 - RI1 (2)
Bit 2 - RI2 (4)
Bit 3 - Humidity Sensor (8)
Bit 4 - DI1 (16)
Bit 5 - DI2 (Not Applicable)
Bit 6 - Time Lost (64)

Содержание SRI-70 Series

Страница 1: ...SRI 70 3 x 0 10Vdc Outputs SRI 71 Digital Input for Overrides Measurement Product sheet MOD3 102 Type SRI 70 71 Model Type Model Description SRI 70 MOD 24 Modbus 3 5 Touchscreen User Interface Built...

Страница 2: ...to 247 via Touchscreen Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable through Touchscreen BACnet BAC models Protocol BACnet MS TP Interface RS485 maximum...

Страница 3: ...24V 24Vac dc Supply 0V 0V Supply Rin1 Remote NTC10 Temperature Sensor Input 1 Rin2 Remote NTC10 Temperature Sensor Input 2 Din Volt Free Digital Input Contact 485A Modbus BACnet MS TP RS485 A Connect...

Страница 4: ...SPLAY SRI 70 WITH FAN SPEED 21 5 C Room 20 1 C A CONTROL MODE AUTO HEATING COOLING FAN VENTILATION FAN The SRI 70 room interface home screen has four touch sensitive areas that allow the system settin...

Страница 5: ...xt parameter in the configuration pages By setting the description to Disabled the sensor reading is not displayed on the screen Note If all sensor displays are Disabled the ACTION CIRCLE displays the...

Страница 6: ...onal user settings options on the SRI room interfaces OFF icon to switch device to OFF OFF icon is displayed here only if OFF icon has been enabled and the PARTY BOOST button has also been enabled LOC...

Страница 7: ...2 Speed 0 Speed 1 Speed 2 Speed 0 Speed 3 A Auto SPEED SET BY NETWORK To set the fan speed or the line bar to a position touch the line bar fan icon area and the line icon and network variable is set...

Страница 8: ...then the fan speed returns to speed 1 Operating Mode Icon The interface unit has Operating Mode icon that allows the unit operating mode to be set network variable 21 5 C Room 23 8 C CONTROL MODE PRE...

Страница 9: ...on Not Visible default ENABLED OFF Icon is displayed in the HOME SCREEN in the FUNCTION BASED ICON area if the PARTY MODE has not been enabled Otherwise it is displayed in the FURTHER SET TINGS SCREEN...

Страница 10: ...he front screen 21 5 C Room 20 1 C LIGHTS STATUS AND ON OFF SWITCH LIGHTS ON LIGHTS OFF A C STATUS AND ON OFF SWITCH A C ON A C OFF When touching the buttons the Lights and or AC Icon are either swith...

Страница 11: ...rnal sensor 2 Res2 fault when activated not connected Built in sensor fault Digital Contact Fault Time Lost SRI P70 only Note If the sensor source has been set to Network then the alarm is inhibited E...

Страница 12: ...levels can be scaled using the AO SP Min and AO SP MAX parameters Humidity Measurement RH option The models with RH option have a 2 rH accurate humidity sensor for room space humidity measurement The...

Страница 13: ...home screen By clicking the icon it is possible to change the displayed language 18 5 C Room 22 7 C EN CLICK TO SET LANGUAGE ES CA BA FR IT PL EN FI SE DE NOTE If the Mode Icon has been activated the...

Страница 14: ...Night 8 Disabled Digital Input Delay Digital Input Delay Timer transition from active to non active 0 7200 seconds Default 0s Internal Sensor Cal Internal Sensor One Point Compensation 10 0 10 0 C F R...

Страница 15: ...meter Name Description Range Brightness Backlight Brightness 0 20 default 5 Enable Lights Enable Lights Icon Network Variable 0 Disabled default 1 Enabled Enable AC Enable AC Icon Network Variable 0 D...

Страница 16: ...LAY Parameter Name Description Range SYSTEM Parameter Name Description Range Address Modbus Address Only Modbus versions BACnet MAC Address Only BACnet versions 0 247 Default 1 0 127 Default 1 Baud Ra...

Страница 17: ...ister 101 needs to be entered Version Software Version x xx Modbus BACnet SYSTEM Parameter Name Description Range Register Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FU...

Страница 18: ...rcentage 2 None 3 Temperature Rel Relative 4 State Select 102 Sensor 3 Source Unsigned 16 0 1 0 Buillt In Sensor Default 1 Network Sensor 103 Sensor 3 Network Temperature Signed 16 580 1220 58 0 122 0...

Страница 19: ...Ventilation 125 Party Mode Boost Time Unsigned 16 0 480 0 480 minutes Default 0 0 Disabled 126 Backlight Brightness Unsigned 16 0 20 0 20 default 5 127 Relay Control Mode Control Controlled by the ti...

Страница 20: ...ned 16 0 59 0 59 146 Current Day P version Unsigned 16 1 31 1 31 147 Current Month P version Unsigned 16 1 12 1 12 148 Current Year P version Unsigned 16 2015 2099 2015 2099 149 Current Hour Update Re...

Страница 21: ...0 1 0 1 Default 0 216 Tuesday Switching Time 2 Target Unsigned 16 0 1 0 1 Default 0 217 Tuesday Switching Time 3 Target Unsigned 16 0 1 0 1 Default 0 218 Tuesday Switching Time 4 Target Unsigned 16 0...

Страница 22: ...t Unsigned 16 0 1 0 1 Default 0 260 Sunday Switching Time 1 Unsigned 16 0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsign...

Страница 23: ...xecute BIBB Object Number Of Instances Instance Assignments Device Object 1 Analog Input 6 AI 0 Sensor 3 Built In Sensor AI 1 Setpoint Calculated AI 2 Humidity Measurement AI 3 Sensor 1 RI1 AI 4 Senso...

Страница 24: ...onfiguration parameters through the SRT touchscreen MutliState Value 7 MSV 0 Ring Colour Read Write 1 White 2 Red 3 Blue 4 Green 5 Orange 6 Yellow 7 Magnenta 8 Cyan 9 Sensor1 10 Sensor2 11 Sensor3 MSV...

Страница 25: ...30 C 40107 Sensor 1 Source Unsigned 0 RI1 1 Network Sensor Default 40109 Fan Manual Control Mode Unsigned 0 Disabled default 1 1 Step 2 2 Step 3 3 Step 4 6 Step 5 1 Step Auto 6 2 Step Auto 7 3 Step Au...

Страница 26: ...d 0 6 40137 Staff Code Unsigned 0000 9999 40138 Language Unsigned 0 English Default 1 Finnish 2 Swedish 3 French 4 Italian 5 Polish 6 Spanish 7 Catalan 8 Euskera 9 Gerrman 40139 Sensor 1 Text RI1 Netw...

Страница 27: ...m Default 5000 40175 Analogue Output at Setpoint Minimum Unsigned 0 100 0 10 0V Default 0 40176 Analogue Output at Setpoint Maximum Unsigned 0 100 0 10 0V Default 100 40300 MAC ID Unsigned 0 127 Defau...

Страница 28: ...SyxthSense Ltd Copyright 2021 SyxthSense Ltd All rights reserved 03 2021 PS MOD3 102 28 29 Online store www syxthsense com Enquiries T 0844 840 3100 E sales syxthsense com...

Страница 29: ...SyxthSense Ltd Copyright 2021 SyxthSense Ltd All rights reserved 03 2021 PS MOD3 102 29 29 Online store www syxthsense com Enquiries T 0844 840 3100 E sales syxthsense com...

Отзывы: