SyxthSense Ltd
Copyright © 2021 SyxthSense Ltd. All rights reserved - 03/2021
PS
MOD3.102
- 20/29
Online store:
www.syxthsense.com
Enquiries: T:
0844 840 3100
E:
138
Language
Unsigned 16
0..9
0 = English (Default)
1 = Finnish
2 = Swedish
3 = French
4 = Italian
5 = Polish
6 = Spanish
7 = Catalan
8 = Euskera
9 = German
139
Sensor 1 Text (RI1/Network)
Default 0 = Disabled
Note: Disabled removes the text and
measurement from the display.
Unsigned 16
0..16
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
140
Sensor 2 Text (RI2/Network)
Default: 0 = Disabled
Note: Disabled removes the text and
measurement from the display.
Unsigned 16
0..15
141
Sensor 3 Text (Built-in / Network Sensor)
Default: 1 = Room
Note: Disabled removes the text and
measurement from the display.
Unsigned 16
0..15
142
Sensor 2 Source
Unsigned 16
0..1
0 = RI1
1 = Network Sensor (Default)
143
Sensor 2 Network Temperature
Signed 16
-580...1220
-58.0...122.0°C/°F (Default 0.0)
159
Disable ECO Button User Cancel
Signed 16
0..1
0 = Enabled (Default)
1 = Disabled
REGISTERS 144 TO 154 ARE FOR SRI-P70/P71 ONLY
144
Current Hour (P-version)
Unsigned 16
0..23
0..23
145
Current Minute (P-version)
Unsigned 16
0..59
0..59
146
Current Day (P-version)
Unsigned 16
1..31
1..31
147
Current Month (P-version)
Unsigned 16
1..12
1..12
148
Current Year (P-version)
Unsigned 16
2015..2099
2015..2099
149
Current Hour Update Register (P-version)
Unsigned 16
0..23
0..23
150
Current Minute Update Register (P-version)
Unsigned 16
0..59
0..59
151
Current Day Update Register (P-version)
Unsigned 16
1..31
1..31
152
Current Month Update Register (P-version)
Unsigned 16
1..12
1..12
153
Current Year Update Register (P-version)
Unsigned 16
2015..2099
2015..2099
154
Update Time (P-version)
Unsigned 16
0..1
0 = No Action
1 = Update
160
CO2 Calibration
Signed 16
-500..+500
-500...+500 ppm
161
Y1 Output Mode
Default: Fan
Unsigned 16
0..7
0 = Network
1 = Sensor1 (RI1)
2 = Sensor2 (RI2)
3 = Sensor3 (Built-In)
4 = Setpoint
5 = Fan
6 = Humidity
7 = CO2
162
Y2 Output Mode
Default: Setpoint
Unsigned 16
0..7
163
Y3 Output Mode
Default: Sensor2 (Built-in)
Unsigned 16
0..7
164
Analogue Output Y1 Override Value
Unsigned 16
0..1000
0..100% (0..10.0V) - Default 0
165
Analogue Output Y2 Override Value
Unsigned 16
0..1000
0..100% (0..10.0V) - Default 0
166
Analogue Output Y3 Override Value
Unsigned 16
0..1000
0..100% (0..10.0V) - Default 0
167
Display CO2
Signed 16
0..1
0 = Enabled (Default)
1 = Disabled
168
Setpoint Limit Mode
Signed 16
0..1
0 = Absolute (Default)
1 = Relative
169
AO Temp Scale
Unsigned 16
0..100
0.100 C/°F (Default 50)
170
AO CO2 Scale
Unsigned 16
0..5000
0..5000ppm (Default 5000)
Register
Parameter Description
Data Type
Raw Data
Range