4.0  MOUNTING INSTRUCTION  

 

4.1  Before mounting  

 
Each fan undergoes a careful inspection at the factory before shipment.  
 
After having removed the packing and before starting to mount the fan, check the following:    

• 

Are there any transportation damages  

• 

Manual test to make sure the impeller is moving without obstructions  

• 

 

4.2  Safety advices for mounting, initial operation, maintenance and service  
 

 

 

 

 

Mounting and electrical connection may only be done by authorized and 
trained personnel and in accordance with valid regulations.  
Each risk to unintendedly touch the impeller has to be avoided (risk to 
damage the impeller!), for example by using a long enough duct or protection 
guard.  
The fan shall be started and operated only after it has been installed into the 
ventilation system or after a protection guard has been installed (SS-EN 294). 
After the fan has been installed, it should be impossible to touch any moving 
parts.  
During mounting, initial operation, maintenance and control the mounting site 
has to be protected in a way that unauthorized people do not have access. 
Any risk to touch the impeller without the intention to do so during above 
mentioned work has to be excluded (switch off the fan and secure against re-
start).  
Only when this risk is excluded, and only when necessary, protection guards 
already mounted to the fan on arrival either at the inlet or outlet may be 
removed.    
All general rules regarding safety of work have to be respected.  
 

 
4.3  Mounting of the fan 

 

• 

Mounting of the fan is shown on attached sketches; access to the fan for maintenance 
purposes has to be possible at any time.  

• 

Fans of type  WVI / WVA may never be installed in explosion hazardous areas.  

• 

Fans of type WVI may be installed within the fire zone 

• 

Cooling air t 

 40°C to cool the motor has to reach the cooling duct of the motor. In case 

the fan can not take the cooling air from the direct surrounding (1m straight, insulated 
duct), any duct pressure losses have to be overcome with an additional auxiliary fan (see 
table): 

 

Size 

400, 450

560, 630

800 

800 

1000 

1000 

Number of poles 

 

 

6 pole 

8 pole 

6 pole 

8 pole 

Minimum cooling air 
volume, 

calculated with  

 t = 20°C, in m

3

/h 

190  380 400 330 570  460 

Minimum cooling air 
volume, 

calculated with  

t = 40°C ,in m

3

/h 

200  400 430 350 610  490 

 

Содержание WVA

Страница 1: ...0 F200 F300 F400 F600 in accordance with EN 12101 3 600 C 120 Min Type WVA F400 and WVI F400 F200 F300 F400 in accordance with EN 12101 3 400 C 120 Min Approval no 99 2121 2 3 TU Munich and appendix of 24 04 2001 Systemair GmbH Seehöfer Str 45 97944 Boxberg Windischbuch Tel 49 0 79 30 92 72 0 Fax 49 0 79 30 92 72 92 info systemair de www systemair de ...

Страница 2: ...NTING INSTRUCTION 4 4 1 Test before mounting 4 4 2 Safety instructions for mounting initial operation maintenance and control 4 4 3 Mounting of the fan 4 4 4 Installation instructions 5 5 0 INITIAL OPERATION 6 6 0 SITE APPROVAL 7 7 0 MAINTENANCE AND CONTROL 7 8 0 FAILURES IN OPERATION 8 9 0 WARRANTY 8 Enclosures Warranty Control sheet Manufacturers declaration ...

Страница 3: ...n be dangerous for human beings and equipment This risk is completely in the hands of the operator 2 0 TECHNICAL DESCRIPTION Casing The casing is manufactured from steel and has lacquer as a finish Impeller The impeller of type WVI WVA F600 is manufactured from stainless steel of type WVI WVA F400 from galvanized steel The impeller is directly connected with the motor shaft by a hub and secured sc...

Страница 4: ... protected in a way that unauthorized people do not have access Any risk to touch the impeller without the intention to do so during above mentioned work has to be excluded switch off the fan and secure against re start Only when this risk is excluded and only when necessary protection guards already mounted to the fan on arrival either at the inlet or outlet may be removed All general rules regar...

Страница 5: ...ature time classification When mounted outside the inlet flange and the cooling duct have to be secured with bird screen and weather protection Fans of type WVA have to be installed outside the fire zone those fans are approved only for installation outside on external wall Place the fan on two steel mounting brackets fixed securely to the external wall Connect the fan at the upper side with a smo...

Страница 6: ...gram is attached to the documentation Another wiring diagram is fixed to the lid of the terminal box Electrical data are attached to these instructions and can also be found on the name plate of the fan at the fan casing As the motors are supplied without thermal protection motor protection devices have to be provided at site Should a frequency inverter be used for daily ventilation purposes the m...

Страница 7: ...rew between motor shaft and hub is fixed tightly and if necessary re fix 3 Verify if the fan impeller is dirty and if necessary clean it 4 Verify the function of all parts relevant for safety 5 Verify the function of the control system 6 Measure the resistance in the windings 7 Measure the operating current 8 Check for eventual vibrations 9 Check if there is excessive noise in the motor bearings T...

Страница 8: ...int and system configuration Should the real system pressure drop be higher than intended some fan types might work in the instable area of the fan curve Contact the service department of the manufacturer Damages or dust on the impeller Clean it eventually it has to be rebalanced or exchanged In case of doubt always contact the service department of the manufacturer After a fire the fan has to be ...

Страница 9: ...iner Aussenwand Kabeleintritt Ansaug Ausblas Kuehlluft Kabeleintritt Ausblas Brandraum Ansaug zugelassener elastischer Anschluss rund oder rechteckig ORVN Ansaug aus einem Kanal an einer Aussenwand ORVN Ansaug aus einem Kanal an einer Aussenwand Kabeleintritt Kuehlluft Brandraum Ausblas Ansaug zugelassener elastischer Anschluss rund oder rechteckig WVI Ansaug aus einem Kanal an einer Außenwand WVI...

Страница 10: ... Kuehlluft Brandraum Ausblas Ansaug Bodenaufstellung ORVN U oder I Profil 80 freie Laenge max 1000 mm zert elastischer Stutzen Wandaufhaengung ORVZ Ausblas U oder I Profil 80 Ansaug wahlweise nur 1 zert Brandraum elastischer Stutzen Wandaufhaengung ORVN Kuehlluft Kabeleintritt Ausblas Brandraum Ansaug U oder I Profil 80 zert elastischer Stutzen Bodenaufstellung WVI Deckenaufhängung WVI Wandaufhäng...

Отзывы: