1.0  APPLICATION 

 
In case of a fire, smoke extract fans are used to exhaust hot air and smoke from buildings. 
They can also be used for normal daily ventilation under normal  operating temperatures. By 
keeping rooms and escape ways free of smoke, rescuing people and protecting the 
installations and material in a room is facilitated. Fire fighting can be done quickly and 
effectively. The building and installations are protected against excessive temperatures, fire 
spreading is prevented.  

• 

To extract smoke up to

 

600°C resp. up to 400°C for min. 120 minutes; 

• 

6 different sizes from 400 up to 1000 

• 

Two different models for different installations are available:  
WVI – installation inside the fire zone,  WVA – installation outside the fire zone 
Fans of type WVI / WVA may never be installed in explosion hazardous areas  

• 

Should the motor be executed in two speeds, normally the low speed is used for daily 
ventilation (medium temperature –20 up to +40°C, if aggressive media are to be 
exhausted, a protection against acids has to be installed), the high speed in case of a fire.

 

 

 

 

Unintended use can be dangerous for human beings and equipment!  
This risk is completely in the hands of the operator.  

 
2.0  TECHNICAL DESCRIPTION  

Casing 

The casing is manufactured from steel and has lacquer as a finish.   

Impeller 

The impeller of type WVI / WVA F600 is manufactured from stainless steel, of type  
WVI / WVA F400 from galvanized steel. The impeller is directly connected with the motor 
shaft by a hub and secured screwed connections. Dynamically balanced in accordance with  
ISO 1940 T1, class G6, 3. 

Motor 

The fans are equipped with three phase motors (400V, 50Hz) without thermal protection. 
Protection class of electric motor IP 54. Insulation class F (IEC). 

 
3.0  TRANSPORT AND STORAGE 

 

3.1 Transport 

 
When leaving the factory, all fans are packed in a way to be protected against normal 
transportation damages. Use suitable lifting devices when transporting the units, to avoid 
harming people or damaging the units.  
 
Avoid unnecessary stress to the unit by pushing it or hitting it with any objects.  Fans may 
only be transported in horizontal position. 
Consider the weight of the fan when transporting it or loading it.  
When taking the goods in arriving at your warehouse do a visual inspection and check if the 
consignment is complete. 
 

3.2 Storage  

 
Until final installation, store the fans in dry places only, protected against weather and dust.  

 

Содержание WVA

Страница 1: ...0 F200 F300 F400 F600 in accordance with EN 12101 3 600 C 120 Min Type WVA F400 and WVI F400 F200 F300 F400 in accordance with EN 12101 3 400 C 120 Min Approval no 99 2121 2 3 TU Munich and appendix of 24 04 2001 Systemair GmbH Seehöfer Str 45 97944 Boxberg Windischbuch Tel 49 0 79 30 92 72 0 Fax 49 0 79 30 92 72 92 info systemair de www systemair de ...

Страница 2: ...NTING INSTRUCTION 4 4 1 Test before mounting 4 4 2 Safety instructions for mounting initial operation maintenance and control 4 4 3 Mounting of the fan 4 4 4 Installation instructions 5 5 0 INITIAL OPERATION 6 6 0 SITE APPROVAL 7 7 0 MAINTENANCE AND CONTROL 7 8 0 FAILURES IN OPERATION 8 9 0 WARRANTY 8 Enclosures Warranty Control sheet Manufacturers declaration ...

Страница 3: ...n be dangerous for human beings and equipment This risk is completely in the hands of the operator 2 0 TECHNICAL DESCRIPTION Casing The casing is manufactured from steel and has lacquer as a finish Impeller The impeller of type WVI WVA F600 is manufactured from stainless steel of type WVI WVA F400 from galvanized steel The impeller is directly connected with the motor shaft by a hub and secured sc...

Страница 4: ... protected in a way that unauthorized people do not have access Any risk to touch the impeller without the intention to do so during above mentioned work has to be excluded switch off the fan and secure against re start Only when this risk is excluded and only when necessary protection guards already mounted to the fan on arrival either at the inlet or outlet may be removed All general rules regar...

Страница 5: ...ature time classification When mounted outside the inlet flange and the cooling duct have to be secured with bird screen and weather protection Fans of type WVA have to be installed outside the fire zone those fans are approved only for installation outside on external wall Place the fan on two steel mounting brackets fixed securely to the external wall Connect the fan at the upper side with a smo...

Страница 6: ...gram is attached to the documentation Another wiring diagram is fixed to the lid of the terminal box Electrical data are attached to these instructions and can also be found on the name plate of the fan at the fan casing As the motors are supplied without thermal protection motor protection devices have to be provided at site Should a frequency inverter be used for daily ventilation purposes the m...

Страница 7: ...rew between motor shaft and hub is fixed tightly and if necessary re fix 3 Verify if the fan impeller is dirty and if necessary clean it 4 Verify the function of all parts relevant for safety 5 Verify the function of the control system 6 Measure the resistance in the windings 7 Measure the operating current 8 Check for eventual vibrations 9 Check if there is excessive noise in the motor bearings T...

Страница 8: ...int and system configuration Should the real system pressure drop be higher than intended some fan types might work in the instable area of the fan curve Contact the service department of the manufacturer Damages or dust on the impeller Clean it eventually it has to be rebalanced or exchanged In case of doubt always contact the service department of the manufacturer After a fire the fan has to be ...

Страница 9: ...iner Aussenwand Kabeleintritt Ansaug Ausblas Kuehlluft Kabeleintritt Ausblas Brandraum Ansaug zugelassener elastischer Anschluss rund oder rechteckig ORVN Ansaug aus einem Kanal an einer Aussenwand ORVN Ansaug aus einem Kanal an einer Aussenwand Kabeleintritt Kuehlluft Brandraum Ausblas Ansaug zugelassener elastischer Anschluss rund oder rechteckig WVI Ansaug aus einem Kanal an einer Außenwand WVI...

Страница 10: ... Kuehlluft Brandraum Ausblas Ansaug Bodenaufstellung ORVN U oder I Profil 80 freie Laenge max 1000 mm zert elastischer Stutzen Wandaufhaengung ORVZ Ausblas U oder I Profil 80 Ansaug wahlweise nur 1 zert Brandraum elastischer Stutzen Wandaufhaengung ORVN Kuehlluft Kabeleintritt Ausblas Brandraum Ansaug U oder I Profil 80 zert elastischer Stutzen Bodenaufstellung WVI Deckenaufhängung WVI Wandaufhäng...

Отзывы: