VR 250 ECH/B 

 

Operation and maintenance instructions 

 
206610 (16-11-2010) 

9

 Systemair 

AB 

   GB 

 

Troubleshooting 

 

 

Fig. 10  
 

Should problems occur, please check or correct the items below before calling your service 
representative. 

1.  Fan(s) do not start 

Check that all fuses and plugs are connected (mains supply and fan plugs). 
 

2. Reduced 

airflow 

a.  Check setting of airflow on control panel. 
b.  Change filter required?  
c.  Cleaning of diffusers/louvers required? 
d.  Cleaning of fans/exchanger block required? 
e.  Is roof unit/air intake clogged? 
f. 

Duct system. Check visible duct runs for damage and/or build-up of dust/pollution.  

g.  Check diffuser/louver openings. 

 

3. 

The unit cannot be controlled (control functions are stuck)

 

Reset control functions by pulling out the plug for 20-30 seconds. 
 

4. Cold 

supply 

air 

a.  Check set supply air temperature on the control panel 
b.  Check if fire thermostat is still alert. If necessary, reset by pressing the red button 

“B”

 

(fig.10)

 in the unit. 

c.  Check if the extract filter needs changing 
d.  Exchanger block does not rotate (defect rotor belt?) 

Possible cause: 

Defect drive belt for the rotating heat exchanger (ensure that the drive 
belt is whole and without any visible damage) 

Defect rotor motor for operation of the rotating heat exchanger (can be 
controlled by pulling the plug of the unit for 10 seconds after which the 
units is restarted. The rotor motor should then restart 

Defect bearings in the heat exchanger rotor (test by rotating the 
exchanger wheel by hand. It should rotate freely)  

The belt pulley on the rotor motor has come loose (check by rotating the 
exchanger wheel by hand and see if the pulley rotates on the motor axis). 
 

5. Noise/vibrations 

a.  Clean fan impellers. 
b.  Pull the fans out and check that screws holding the fans are tightened. 

 

Содержание VR-250 ECH/B

Страница 1: ...10 02 16 11 2010 VR 250 ECH B Air Handling Unit Operation and maintenance instructions GB GB...

Страница 2: ...operation 5 Manual summer operation 5 Kitchen extraction 6 Maintenance 7 Changing extract inlet filter 7 Changing operation time between filter changes 7 Checking the heat exchanger 8 Checking the fa...

Страница 3: ...ply of filtered and preheated outdoor air to residential areas and extract of a corresponding amount of used air from wet rooms and kitchen The unit is equipped with a heat exchanger block to ensure s...

Страница 4: ...hange Signal heater battery ON Fig 2 The unit is controlled from a separate controller with the following functions Airflow Fan speed Buttons to increase or decrease airflow in 3 steps 4 and 5 fig 2 L...

Страница 5: ...ated but the efficiency will be reduced if the filter is not replaced Operation time 6 9 or 12 months between filter changes can be set on the control panel see installation instructions From factory...

Страница 6: ...cooker is led directly through the extract fan and not through the heat exchanger The capacity of the extract fan is then primarily used for extract from the cooker but a minor airflow is maintained...

Страница 7: ...y Contact your supplier for new filter Operation time between filter changes must be re set after filter change Press button 13 fig 2 for approx 5 seconds Yellow lamp 14 and one of the green lamps 6 7...

Страница 8: ...sary the fans can be pulled out for cleaning with a soft brush Do not use water White spirit can be used to remove obstinate settlements Allow to dry properly before remounting Cleaning extract louver...

Страница 9: ...pulling out the plug for 20 30 seconds 4 Cold supply air a Check set supply air temperature on the control panel b Check if fire thermostat is still alert If necessary reset by pressing the red butto...

Страница 10: ...nintended rotor stop belt breakage defective motor 1 1 Missing zero crossing detector 1 1 Voltage too low 210 V Lamps 6 7 and 8 are flashing in accordance with set inlet air temperatures see Operation...

Страница 11: ...10 02 Systemair AB Industriv gen 3 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www systemair com 206610 16 11 2010...

Отзывы: