4.2. ELECTRICAL SPECIFICATIONS FOR STANDARD MOTORS
Motors - 230 V / 1 ph / 50 Hz / 60 Hz
Electric heating resistances - 230 V / 1 ph / 50 Hz / 60 Hz
(*) Current and power drawn by the motor in operation at 230 V / 1 Ph / 50 Hz, unit not fitted with ducting
and with 0 Pa pressure available for a unit with a G3 filter. Rectangular duct inlet and outlet
(*) Current and power drawn by the motor in operation at 230 V / 1 Ph / 50 Hz, unit not fitted with ducting
and with 0 Pa pressure available for a unit with a G3 filter. Circular duct inlet and outlet.
4.3. ELECTRIC HEATING RESISTANCES
Unit size
VH07
VH15
VH18
Current
absorbed
(A) *
Power
absorbed
(w)*
Current
absorbed
(A) *
Power
absorbed
(w)*
Current
absorbed
(A) *
Power
absorbed
(w)*
Speed
V1
0.66
132
0.93
180
0.93
180
V2
0.75
163
1.33
271
1.33
271
V3
0.82
182
2.00
421
2.00
421
V4
0.88
201
2.52
587
2.52
587
V5
0.98
222
3.17
675
3.17
675
Unit size
VH21
VH24
VH27
Current
absorbed
(A) *
Power
absorbed
(w)*
Current
absorbed
(A) *
Power
absorbed
(w)*
Current
absorbed
(A) *
Power
absorbed
(w)*
Speed
V1
0.93
180
2.00
420
2.00
420
V2
1.33
271
2.40
530
2.40
530
V3
2.00
421
3.00
673
3.00
673
V4
2.52
587
3.85
870
3.85
870
V5
3.17
675
Unit size
Capacity (W)
BE1
BE2
BE3
VH07
1000
1500
2000
VH15 / VH18 / VH21
1000
2000
3000
VH24 / VH27
1000
2000
3000
SEE APPENDIX
4.4. DIMENSIONS
Содержание VH07
Страница 2: ......
Страница 25: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Страница 34: ...CODE 3991108 4 2 V1 V2 V3 V4 V5 BMS BMS GND 12V RCW RCW X VH APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO VH07 AQUANET...
Страница 42: ...XVIII VH APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO...
Страница 43: ......