Topvex TX03-06 

 

 Operation and Maintenance instructions 

 

205875

 

 

Systemair AB

 

8

 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Display shows 

Description

Set

 the status for 

Cooling

 to Active or Not Active. Preset is: Not Active. 

Function: Controls a cold-water cooling battery with a 0-10 V DC signal. 
 

Reset filter alarm

 by setting the Reset alarm to Yes. 

 
 

Filter alarm 

 

Set

 the time until the filter alarm should be activated, 1-15 months. 

Functions 

 

Set

 the status for 

Fire function 

to Active or Not Active. Preset is: Not 

Active. 

Set

 how the unit should operate if the fire alarm function is activated, run 

on High fan-speed or Shut off. Preset is: Shut off. 
Function: Decides how the unit should operate at fire alarm. 

Set

 the status for 

Cool Recycling

 to Active or Not Active. Preset is: Not 

Active. 
Function: Closes the by-pass damper to allow recovery of the cold 
extract air. Is activated when the extract air temperature is 3K lower than 
the outdoor air temperature.  
 

Set 

the status for

Free cooling 

to Active or Not Active. Preset is: Not 

Active 
Function: Starts the fans and opens the by-pass damper under certain 
conditions to use the cooler outdoor air to cool down the interior of the 
building during night time between 

Start Cooling Hour (0:00)

 and 

Stop 

Cooling Hour(06:00)

.  

Free cooling active: Yes 

(changeable, Yes or No)

 

Outdoor temp activation 22°C

 (changeable, the average daytime temp. 

needs to be over this value in order to start the function) 
 
 

Outdoor temperature night 
High: 15,0°C

 (changeable, Outdoor temp. needs to be below this value 

to start the function) 

Low: 5,0°C

 (changeable, Outdoor temp. needs to be over this value to 

start the function) 

Room temperature min: 18,0°C

 (changeable, Room temp. (extract air 

temp. sensor) needs to be over this value to start the function) 

Содержание TopVex TX03

Страница 1: ...Corrigo ver no 1 2 1 00 Topvex TX03 TX04 TX06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Страница 2: ...of contents 2 Warning 2 Operation 3 General 3 Free cooling 3 Defrost function general description 4 Defrost levels 4 Shortcut to set the menu language 5 Control panel 5 How to operate 5 Navigating th...

Страница 3: ...owing criteria are met simultaneously all time channels are in OFF position and that the unit goes back to normal operation the following day set operation time during the following 24 hours the avera...

Страница 4: ...preset number of minutes the by pass damper inside the unit opens to help reduce the flow of the cold outdoor air through the heat exchanger block As this cycle is initiated the set supply air tempera...

Страница 5: ...arm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button 7d Brown cable 6 Mounting holes 7e Black cable Fig 1 How to operate The menus in the Corrigo E con...

Страница 6: ...menus through which you may move using the UP DOWN buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the displ...

Страница 7: ...emperature value 16 30 C Running mode Set the running mode of the unit Choose between Auto Manual high Manual medium Manual low or Manual shut off Time Date Set the present time date and weekday Set t...

Страница 8: ...or Not Active Preset is Not Active Function Closes the by pass damper to allow recovery of the cold extract air Is activated when the extract air temperature is 3K lower than the outdoor air temperatu...

Страница 9: ...y air fan SAF in of maximum fan speed Choose between 0 to 100 All fan speeds LOW MEDIUM HIGH can be set in this interval Display shows Description Defrost function Set the By pass function to Yes or N...

Страница 10: ...ignal 0 10V Set the status to Auto Manual or Off In Manual status it is possible to set the output signal within a range from 0 to10V more than 2V activates the electrical re heater on off function AO...

Страница 11: ...is by pressing the OK button at the same time as the main voltage is switched on 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active Modbus Active Modbus address...

Страница 12: ...d from Systemair Operation time between filter changes must be reset after filter change see page 8 Filter alarm To change the alarm activating time see page 8 Filter alarm Initial pressure drop over...

Страница 13: ...s and louvers are mounted in ceilings walls in bedroom living room wet rooms WC etc Remove diffusers and louvers and wash in hot soapy water if required Diffusers louvers must be put back with their o...

Страница 14: ...ake clogged Check ducts for visible damage and or build up of dust pollution Check diffuser louver openings 3 Cold supply air Check the control temperature on the control panel Check if the overheatin...

Страница 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Страница 16: ...35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240 Minutes Minutes Filter alarm Replaces interval 6 Months Months...

Страница 17: ..._____________________________________________________________________________________________________ Topvex TX03 06 Operation and Maintenance instructions 205875 Systemair AB 17 Notes...

Страница 18: ...rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www s...

Отзывы: