Topvex TX03-06 

 

 Operation and Maintenance instructions 

 

205875

 

 

Systemair AB

 

9

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Show

 the Analogue inputs. 

AI1

: Show the actual temperature of the supply air. 

AI2

: Show the actual temperature of the exhaust air. 

AI3 applies only to HW units. 
AI3

: Show the actual temperature of the return water in the hot water        

battery (frost protection). 

AI4:

 Show the actual outdoor temperature 

 

In-/Outputs 

 

Set

 the 

Air control

 mode to: 

 Supply. 

 

Supply & Outdoor compensation. 

 

Set

 how much the control temp. should be compensated when the   

out door temperature is –20°C and +15°C (the compensation will be 
linear between these two points). 
E.g. At –20 : 5°C. 
E.g. At +15 : -2°C. 
Control temp. = 18°C. 
Outdoor temperature –20°C gives a Control temp. of 23°C (18+5). 

  Outdoor tempe15°C gives a Control temp. of 16°C (18-2). 

 Extract. 

 

  Set

 the permitted maximum and minimum supply air temperature. 

Set

 the 

Fan speed control

 for the supply air fan 

(SAF) 

in % of 

maximum fan speed. Choose between: 0% to 100%. 
All fan speeds LOW, MEDIUM & HIGH can be set in this interval 

Display shows 

Description

Defrost function
Set 

the 

By-pass function 

to 

“Yes” 

or 

“No” 

(preset is 

“No”

Function: 

(enables the use of the by-pass damper for 

defrosting. The set supply air temperature is reduced 4K during 
defrost cycle. Reduction of both supply air fan and extract air 
fan speed up to 20% if supply air temperature does not reach 
reduced set point. If necessary the supply air fan is stopped 
completely during the defrosting cycle (stop defrosting)). 

Set 

the 

Reduced supply air 

to 

“Yes” 

or 

“No” 

(preset is 

“No”

Function: Reduces the supply air fan speed up to 20% 
whenever there is a frost risk of the plate heat exchanger. 

Set 

the defrost level between 1 and 5 (preset is 3) 

Function: Level 1 to 5 are depending on the estimated indoor 
relative humidity level. See table 1 on page 4 for a 
description of the different levels.

 

 

Automatic summer/wintertime changeover 

Choose between “Yes” and “No”, preset is “Yes”.  
 

Set

 the 

Fan speed control

 for the exhaust air fan 

(EAF)

 in % of 

maximum fan speed. Choose between: 0% to 100%. 
All fan speeds LOW, MEDIUM & HIGH can be set in this interval 

Содержание TopVex TX03

Страница 1: ...Corrigo ver no 1 2 1 00 Topvex TX03 TX04 TX06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Страница 2: ...of contents 2 Warning 2 Operation 3 General 3 Free cooling 3 Defrost function general description 4 Defrost levels 4 Shortcut to set the menu language 5 Control panel 5 How to operate 5 Navigating th...

Страница 3: ...owing criteria are met simultaneously all time channels are in OFF position and that the unit goes back to normal operation the following day set operation time during the following 24 hours the avera...

Страница 4: ...preset number of minutes the by pass damper inside the unit opens to help reduce the flow of the cold outdoor air through the heat exchanger block As this cycle is initiated the set supply air tempera...

Страница 5: ...arm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button 7d Brown cable 6 Mounting holes 7e Black cable Fig 1 How to operate The menus in the Corrigo E con...

Страница 6: ...menus through which you may move using the UP DOWN buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the displ...

Страница 7: ...emperature value 16 30 C Running mode Set the running mode of the unit Choose between Auto Manual high Manual medium Manual low or Manual shut off Time Date Set the present time date and weekday Set t...

Страница 8: ...or Not Active Preset is Not Active Function Closes the by pass damper to allow recovery of the cold extract air Is activated when the extract air temperature is 3K lower than the outdoor air temperatu...

Страница 9: ...y air fan SAF in of maximum fan speed Choose between 0 to 100 All fan speeds LOW MEDIUM HIGH can be set in this interval Display shows Description Defrost function Set the By pass function to Yes or N...

Страница 10: ...ignal 0 10V Set the status to Auto Manual or Off In Manual status it is possible to set the output signal within a range from 0 to10V more than 2V activates the electrical re heater on off function AO...

Страница 11: ...is by pressing the OK button at the same time as the main voltage is switched on 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active Modbus Active Modbus address...

Страница 12: ...d from Systemair Operation time between filter changes must be reset after filter change see page 8 Filter alarm To change the alarm activating time see page 8 Filter alarm Initial pressure drop over...

Страница 13: ...s and louvers are mounted in ceilings walls in bedroom living room wet rooms WC etc Remove diffusers and louvers and wash in hot soapy water if required Diffusers louvers must be put back with their o...

Страница 14: ...ake clogged Check ducts for visible damage and or build up of dust pollution Check diffuser louver openings 3 Cold supply air Check the control temperature on the control panel Check if the overheatin...

Страница 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Страница 16: ...35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240 Minutes Minutes Filter alarm Replaces interval 6 Months Months...

Страница 17: ..._____________________________________________________________________________________________________ Topvex TX03 06 Operation and Maintenance instructions 205875 Systemair AB 17 Notes...

Страница 18: ...rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www s...

Отзывы: