 Operation and Maintenance instructions 

 

205875

 

 

Systemair AB

 

10

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Show

 the status and settings of the digital inputs. 

DI1

: Fan alarm. Connected to the thermal contact in the fan motor. Stops 

the fan and disconnect the electrical heater when the alarm is activated. 

DI2: applies only to EL units. 
DI2

: Overheating of the electrical heater. Connected to the thermal 

contact in the heater. Disconnects the heater when the alarm is 
activated. 

DI3

: Timer/P.B. Starts the Extended running when an external contact, 

Timer or Push button, closes. Only when the unit is running in Off mode. 

DI4

: Not in use 

DI5: Is only shown when the Fire function is activated. 
DI5

: Fire alarm. Connects to an external fire central. Stops the unit or 

changes the fan speed to High if the alarm is activated. 

Show and Set

 the Analogue outputs. 

AO1

: Heating battery, Electric or hot-water. Show the output signal, 0-  

10V. Set the status to: Auto, Manual or Off. In Manual status it is 
possible to set the output signal within a range from 0 to10V, more than 
2V activates the electrical re-heater (on/off function). 

AO2 is shown only when the cooling function is activated. 
AO2

: Cooling battery, cold-water. Show the output signal, 0-10V. Set 

the status to: Auto, Off or Manual. In Manual status it is possible to set 
the output signal within a range from 0 to10V. 

AO3:

 Control signal, 0-10V, to the extract air fan, Set Auto, Man or Off 

AO4:

 Control signal, 0-10V, to the supply air fan, Set Auto, Man or Off 

AO5:

 Control signal, 0-10V, to the by-pass damper, Set Auto, Man or 

         Off 
 

Show and Set

 the digital outputs, output 24V AC. 

DO1

: Damper motor on/off. Opens the damper when the unit is started 

DO2

: Not in use 

DO3

: Not in use 

DO4

: Not in use  

DO5

: Alarm output. Show the status. 

 

Configuration 

 

Version 

 

Show

 the program version 

Present version 

1.2-1-00

 

(Enter into the configuration menu using code

8642

)

1. AHU type 

(Preset from factory is Topvex-X), 

should normally not 

be changed 
        

 

Fan speed control SAF 

(Supply air fan) 

          

High: 100% 

(changeable 0-100%) 

          

Medium: 75%

 (changeable 0-100%) 

           

Low: 35%

 (changeable 0-100%)

 

Display shows 

Description

Содержание TopVex TX03

Страница 1: ...Corrigo ver no 1 2 1 00 Topvex TX03 TX04 TX06 Compact Air Handling Unit Operation and Maintenance instructions GB GB...

Страница 2: ...of contents 2 Warning 2 Operation 3 General 3 Free cooling 3 Defrost function general description 4 Defrost levels 4 Shortcut to set the menu language 5 Control panel 5 How to operate 5 Navigating th...

Страница 3: ...owing criteria are met simultaneously all time channels are in OFF position and that the unit goes back to normal operation the following day set operation time during the following 24 hours the avera...

Страница 4: ...preset number of minutes the by pass damper inside the unit opens to help reduce the flow of the cold outdoor air through the heat exchanger block As this cycle is initiated the set supply air tempera...

Страница 5: ...arm LED 7a Yellow cable 3 Write enable LED 7b Orange cable 4 OK button 7c Red cable 5 Clearing button 7d Brown cable 6 Mounting holes 7e Black cable Fig 1 How to operate The menus in the Corrigo E con...

Страница 6: ...menus through which you may move using the UP DOWN buttons Sometimes there are further sub menus linked to a menu or menu item This is indicated by an arrow symbol at the right hand edge of the displ...

Страница 7: ...emperature value 16 30 C Running mode Set the running mode of the unit Choose between Auto Manual high Manual medium Manual low or Manual shut off Time Date Set the present time date and weekday Set t...

Страница 8: ...or Not Active Preset is Not Active Function Closes the by pass damper to allow recovery of the cold extract air Is activated when the extract air temperature is 3K lower than the outdoor air temperatu...

Страница 9: ...y air fan SAF in of maximum fan speed Choose between 0 to 100 All fan speeds LOW MEDIUM HIGH can be set in this interval Display shows Description Defrost function Set the By pass function to Yes or N...

Страница 10: ...ignal 0 10V Set the status to Auto Manual or Off In Manual status it is possible to set the output signal within a range from 0 to10V more than 2V activates the electrical re heater on off function AO...

Страница 11: ...is by pressing the OK button at the same time as the main voltage is switched on 4 Display unit type E DSP preset 5 Modbus Comm Not Active or Active Preset is Not Active Modbus Active Modbus address...

Страница 12: ...d from Systemair Operation time between filter changes must be reset after filter change see page 8 Filter alarm To change the alarm activating time see page 8 Filter alarm Initial pressure drop over...

Страница 13: ...s and louvers are mounted in ceilings walls in bedroom living room wet rooms WC etc Remove diffusers and louvers and wash in hot soapy water if required Diffusers louvers must be put back with their o...

Страница 14: ...ake clogged Check ducts for visible damage and or build up of dust pollution Check diffuser louver openings 3 Cold supply air Check the control temperature on the control panel Check if the overheatin...

Страница 15: ...el size Series no Filter replaces interval set Present time and date set Week scheduler settings Preset On time is Period 1 07 00 16 00 Monday Sunday Medium fan speed Period 2 00 00 00 00 Monday Sunda...

Страница 16: ...35 of max Fan speed Fan speed Medium 75 of max Fan speed Fan speed Maximum 100 of max Fan speed Extended Forced running Running time 240 Minutes Minutes Filter alarm Replaces interval 6 Months Months...

Страница 17: ..._____________________________________________________________________________________________________ Topvex TX03 06 Operation and Maintenance instructions 205875 Systemair AB 17 Notes...

Страница 18: ...rights at any time without prior notice make changes and improvements to the contents of this manual Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Phone 46 222 440 00 Fax 46 222 440 99 www s...

Отзывы: