Topvex TR800, TR1300, TR1800, TR4000

Compact Air Handling Unit

Operation and Maintenance 

Instructions

Item# 415005

2022-05-13

Содержание Topvex TR1300

Страница 1: ...Topvex TR800 TR1300 TR1800 TR4000 Compact Air Handling Unit Operation and Maintenance Instructions Item 415005 2022 05 13...

Страница 2: ...ing the Control Panel 8 4 Commissioning 9 4 1 Before Starting the System 9 4 2 Initial Setup of the Unit 9 4 3 Menu Overview Operator Service Level 12 4 4 Free Cooling Description 23 4 5 Cooling Recov...

Страница 3: ...er Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work All electrical connections must be carried out in accordance with local rules and re...

Страница 4: ...ir D Connection exhaust air 1 Fan supply air 2 Fan extract air 3 Filter extract air 4 Filter outdoor air 5 Heat exchanger 6 Rotor motor 7 Rotor belt 8 Re heater electric or hydronic 9 Pre heater elect...

Страница 5: ...wg 40Pa and 1 2 in wg 300 Pa The pressure switch is preset from factory to 1 0 in wg 240 Pa 2 2 2 Outdoor and Extract Air Filters and Pre Filter The filters are of bag filter type with filter quality...

Страница 6: ...t See HWC EPH Installation Instructions manual 420353 for correct procedure In Topvex FR800 3800 all temperature sensors are mounted and wired inside the unit except for the supply air sensor which is...

Страница 7: ...For pre heater components please refer to the Pre Heater installation instructions 420353 Fig 3 Electrical components Topvex TR800 1800 EL Position Description 1 Controller E 28 UC 2 Transformer 208...

Страница 8: ...ormer 208 230 24VAC TR24 3 Terminals for internal and external components TB3 4 Terminals for internal wiring TB2 5 Terminals for main power voltage to the unit TB1 6 Contactor K1 On Off rotor motor 7...

Страница 9: ...TR4000 Position Description 1 Controller E 28 UC 2 Transformer 208 230 24VAC TR24 3 Terminals for internal and external components TB3 4 Terminals for internal wiring TB2 5 Terminals for main power v...

Страница 10: ...D Indicates alarm by flashing red light 3 Write LED Indicates by flashing yellow light that parameters can be set or changed 4 OK button Press this button to be able to change or set parameters whenev...

Страница 11: ...stallation instructions The unit is correctly wired Sound attenuators if used are installed and that the duct system is correctly connected to the unit Outdoor air intake is positioned with sufficient...

Страница 12: ...HT to select next digit Press OK to confirm and enter Per 2 START time Change time using the UP DOWN arrow buttons Press RIGHT to select next digit Press OK to confirm and enter Per 2 STOP time Change...

Страница 13: ...ext digit Press OK to confirm and enter Per 2 START time Change time using the UP DOWN arrow buttons Press RIGHT to select next digit Press OK to confirm and enter Per 2 STOP time Change time using th...

Страница 14: ...to the Service level in the table below are marked with grey background color To logon to the Service level use code 2222 under Access rights Main menu item Sub menu item 1 Sub menu item 2 Explanation...

Страница 15: ...of the cooling recovery function External set point Not active Shows the status of the external set point Alarm events Shows all registered alarms along with the time and date they occurred Move down...

Страница 16: ...perature in the water heating coil Only visible for HW units Exhaust air temp Actual F Shows the actual exhaust air temperature Efficiency Exchanger Actual Shows the actual heat recovery efficiency Th...

Страница 17: ...figured for Flow control Flow control EAF Setp 1 1 647 4 CFM Setp 1 2 323 7 CFM Set the normal 1 1 and reduced 1 2 airflow for the extract air fan Outdoor comp Setp 1 4 F 5 9 CFM 32 F 0 CFM Act Comp 0...

Страница 18: ...ternal pressure set point for normal speed 1 1 and reduced speed 1 2 for the supply air fan Outdoor comp Setp 1 4 F 0 in wg 50 F 0 in wg Act Comp 0 in wg Set the EAF pressure compensation for the sett...

Страница 19: ...number of consecutive days from one and upwards The dates are in the format MM DD When the current date falls within a holiday period the scheduler will use the settings for the weekday Holiday Manua...

Страница 20: ...put 0 100 Cooling Auto Manual set 0 0 Set the cooling to Auto Manual or Off Set the manual output 0 100 Note Needs to be activated in order to be visible here P1 Heating Auto P1 Exchanger Auto Set the...

Страница 21: ...Set P band and I time for the Shutdown function Note See Corrigo E ventilation manual for deeper explanation Frost protection Active Setp shutdown 77 0 F P band active 41 0 F P band active 41 F means...

Страница 22: ...ser settings they were saved as earlier Select Yes or No Save user settings No The current configuration can be saved in a separate memory area and can later be restored using the previous menu Restor...

Страница 23: ...t the delay in minutes from the time when the free cooling sequence has stopped until a possible heating sequence is initiated i e how long a cooler room temperature than set temperature can be accept...

Страница 24: ...limit 5 Set the humidity control to Humid Dehumidification Dehumidification Humidification or Not active Set the start limit and stop limit in RH Applicable for external Humidification or Dehumidific...

Страница 25: ...tart and stop temperature intervals Stop conditions Outdoor temp above the set max value 64 4 F 18 C or below the set min value condensation risk 50 F 10 C The room temp extract air temp is below the...

Страница 26: ...ir for a defined period of time preventing any frost build up before going back to normal ventilation mode Recirculation There are 3 different recirculation configurations First is a 5th port configur...

Страница 27: ...at a proper lifting device is used Use protective clothing Caution If the unit is installed in a cold place make sure that all joints are covered with insulation and tape well Duct connections duct en...

Страница 28: ...be ordered from Systemair Operation time between filter changes depends on the air pollution at the installation site A differential pressure switch indicates when it s time to change the filters This...

Страница 29: ...g 8 Removing the fans Fig 7 Removing the heat exchanger Note Make sure that the rotor motor is not exposed to moisture After extended use dust may build up in the exchanger and block the air flow It i...

Страница 30: ...rs dust may have deposited on the surface of the coil This may reduce coil capacity The coil can be cleaned with a pressure washer with misting jets or with compressed air Cleaning should be carried o...

Страница 31: ...torques at the edge of the cover using a small screwdriver and at the same time pulling the edges outwards 2 Grip the battery firmly with your fingers and lift it upwards until it rises from its holde...

Страница 32: ...ting in control panel schedules auto manual operation airflow set points etc 2 Wheel motor does not start Check if there are any alarm messages Check if the automatic fuse AS1 is tripped figure 3 pos...

Страница 33: ...31 6 Service Before calling your service representative make a note of the specification and production number from the type label figure 9 Fig 9 Type label Position Description 1 Model number 2 Item...

Страница 34: ...Topvex TR800 TR1300 TR1800 TR4000 Operation and Maintenance Instructions Systemair Inc 32 Notes...

Страница 35: ...Topvex TR800 TR1300 TR1800 TR4000 Operation and Maintenance Instructions Systemair Inc 33 Notes...

Страница 36: ...improvements to the contents of this manual without prior notice Systemair Inc 50 Kanalflakt Way Bouctouche NB E4S3M5 Canada Phone 1 800 263 7081 10048 Industrial Blvd KS 66215 United States Phone 1...