Topvex TR800, TR1300, TR1800, TR4000
Operation and Maintenance Instructions
Systemair Inc.
16
Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
Outdoor
comp.Setp. 1
-4°F = 0 in.wg
50°F = 0 in.wg
Act. Comp: 0
in.wg
Set
the SAF pressure
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive or
negative.
Shows
the actual pressure
compensation.
Pressure
control EAF
Actual: in.wg
Setp.: in.wg
Shows
the actual external
pressure and set point for the
extract air fan.
Only visible if the unit is
configured for “Pressure
control: (VAV)
Pressure
control EAF
Setp 1/1: 1.0
in.wg
Setp 1/2: 0.4
in.wg
Set
the external pressure set
point for normal speed (1/1)
and reduced speed (1/2) for the
supply air fan.
Outdoor
comp.Setp. 1
-4°F = 0 in.wg
50°F = 0 in.wg
Act. Comp: 0
in.wg
Set
the EAF pressure
compensation for the settable
outdoor temperature. The
outdoor compensation is linear
and is set using two parameter
pairs which give the value of the
compensation at two different
outdoor temperatures. The
compensation can be positive or
negative.
Shows
The actual pressure
compensation.
→ Time settings
→ Time/Date
Set
correct time and date.
→ Timer normal
speed
Set
week schedule Monday to
Holiday for normal
speed. Possible to set 2 periods
per day.
00:00 24:00 for continuous
running. 00:00 00:00 inactivates
the period.
Note the settings in the
commissioning record
→ Timer reduced
speed
Set
week schedule Monday to
Holiday for reduced
speed. Possible to set 2 periods
per day.
00:00 24:00 for continuous
running. 00:00 00:00 inactivates
the period.
Note the settings in the
commissioning record