Topvex TR800, TR1300, TR1800, TR4000
Operation and Maintenance Instructions
Systemair Inc.
13
Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
Free cool
active: No
Shows
the status of the free
cooling function
Support control
Active: No
C02/VOC active
Never
Shows
the status of the support
control function
Shows
the status of the
demand ventilation (C02/VOC)
function
Fire damper
function
Not active
Operation when
alarm
Stopped
Shows
the status of the fire
damper function
Frost
protection
Active
Cooling
recovery
No
Shows
the status of the frost
protection function
Shows
the status of the cooling
recovery function
External set
point
Not active
Shows
the status of the external
set point
→ Alarm events
Shows
all registered alarms
along with the time and date
they occurred
Move down and up in the list by
pressing ↑↓
→ Input/ Output → Analogue
inputs
Shows
the status of the
Analogue inputs
→ Digital
inputs
Shows
the status of the Digital
inputs
→Universal
inputs
Shows
status of Universal
Analogue inputs
Shows
status of Universal
Digital inputs
→Analogue
outputs
Shows
the status of the
Analogue outputs
→Digital
outputs
Shows
the status of the Digital
outputs
→Temperature
Extract air
temp
Act.: °F
Setp: 64.4°F
Shows
the configured
temperature control (Default is
Extract air temp
)
Shows
the actual temperature
in the chosen control mode
Shows
the temperature for the
chosen control mode