Product description |

3

2.2

Description of internal components

2.2.1

Supply and extract air fans

The fans have external rotor motors of EC type which are steplessly controlled individually by setting the control signal
to a fixed value. It is possible to program the speed in 2 steps (normal/reduced) depending on the programming of the
week schedule. The motor bearings are life time lubricated and maintenance free. It is possible to remove the fans for
cleaning, see chapter for more information.

2.2.2

Pressure sensor fans/filters

Two pressure sensors are installed (figure 1), each of the sensors has two functions. One function is to measure the dif-
ferential pressure over the inlet cone of the fan impellers to maintain the airflow at constant level (CAV function as
standard). The other function, is to measure the differential pressure over the supply and extract air filters so that when
the pressure drop reaches the set value, an alarm is triggered in the main regulator, which indicates that the filter needs
to be replaced.

2.2.3

Supply and extract air filters

The filters are of bag filter type with filter quality ePM1 60% (F7) for the supply air filter and ePM10 60% (M5) for the
extract air filter. The filters need to be replaced when polluted. New sets of filters can be acquired from your installer or
wholesaler.

2.2.4

Heat exchanger

Topvex SX/C, TX/C models are equipped with a counter flow heat exchanger and a by-pass damper. The operation of
the by-pass damper is automatic and depends on the set temperature or if deicing is in operation.

For defrosting a pressure transmitter is installed which measure the differential pressure over the heat exchanger.

2.2.5

Switch module

A switch module with HMI and 2 TCP/IP connections is mounted in the heat recovery units. Connection is made through
the panel outlet in the air handling unit (see figure 2).

Note:

24V HMI connection dedicated for the display. The connection is only for HMI and no other

connections is permitted.

2.2.6

Temperature sensor

5 temperature sensors (PT1000) are included in the unit from factory. The sensors are as follows:

• Supply air sensor

• Extract air temperature sensor

• Outdoor air temperature sensor

• Exhaust air temperature sensor

• Efficiency temperature sensor

2.2.7

Water heating battery

In units with built in water heating battery the hot water coil is located next to the supply air connection. The hot water
coil can be either HWL (hot water coil, low power) or HWH (hot water coil, high power). The coil material is copper pip-
ing with a frame of galvanized sheet steel and aluminium fins. The coil is equipped with venting and immersion sensor
for frost protection.

2.2.8

Electrical heater

In units with built in electrical heater the heating rods are located after the supply air fan in the airflow direction. The
material is stainless steel. The electrical heating battery has both automatic and manual overheating protection. The
manual overheat protection is reset by pushing the red button on top of the electrical heater frame (pos. 10 figure 2).
The power demand of the electric heating coil is controlled by the main regulator, which controls the heat steplessly by
a TTC triac control according to the selected control function that is set in the control panel.

154394 | A001

Содержание Topvex SX/C

Страница 1: ...Document in original language 154394 A001 Topvex SX C Topvex TX C Air Handling Unit Operation and Maintenance Instructions GB...

Страница 2: ...Systemair AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously...

Страница 3: ...escription 4 2 2 10 Section defrosting 5 2 3 Internal components electrical connection box 6 3 Maintenance 7 3 1 Important 7 3 2 Maintenance intervals 7 3 3 Maintenance instruction 8 3 3 1 Changing su...

Страница 4: ......

Страница 5: ...ies Caution Indicates a risk of damaging the product or prevent optimal operation Important This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory...

Страница 6: ...ply air 2 Fan extract air 3 Filter supply air 4 Filter extract air 5 Heat exchanger 6 Electrical connection box 7 Damper by pass outdoor air 8 Pressure transmitter supply air fan extract air filter 9...

Страница 7: ...icing is in operation For defrosting a pressure transmitter is installed which measure the differential pressure over the heat exchanger 2 2 5 Switch module A switch module with HMI and 2 TCP IP conne...

Страница 8: ...s the night temperature indoor and outdoor temperature during 3 minutes at the set starting hour when the fans are started so that the sensors can perform a temperature measurement If above conditions...

Страница 9: ...will start After stop defrosting the unit will re start If the pressure does not decrease the air handling unit is stopped and an alarm is shown in the display Make sure that the ice is melted before...

Страница 10: ...ts 4 Terminals for internal wiring 5 Terminals for mains power supply to the unit 6 Contactor K2 On Off Pump control water HW units only not present in EL units 7 Automatic fuse 8 Automatic fuse for h...

Страница 11: ...eware of hot surface on the heating battery during maintenance and service 3 2 Maintenance intervals The table below shows recommended maintenance intervals for the unit and the installation To ensure...

Страница 12: ...an alarm in the control panel When this occurs do the following 1 Replace the filters with new ones as described below 2 Press on the alarm symbol on the control panel 3 Choose Filter alarm and press...

Страница 13: ...o be vented to maintain the batteries capacity 3 3 5 Checking the electrical heating battery After long period of time dust and pollutants can build up on the heating rods This can cause unpleasant od...

Страница 14: ...up capacitor saves the memory and keeps the clock running for at least 10 minutes after the power supply is removed Therefore if the battery replacement takes less than 10 minutes there will be no nee...

Страница 15: ...if diffusers and louvres need cleaning Check diffuser louvre openings Check if fans and exchanger block need cleaning Check if the roof unit or air intake is clogged Check ducts for visible damage an...

Страница 16: ...0V 25 A 50Hz Systemair Sverige AB Industriv gen 3 SE 73930 Skinnskatteberg Sweden 4016 W IP23 225kg Ver A Serial no 1234 567891 0001 140214 Topvex XXXX 16kW 16kW www systemair com 2 3 4 5 Fig 3 Type l...

Страница 17: ...154394 A001...

Страница 18: ......

Страница 19: ......

Страница 20: ...C Topvex TX C Operation and Maintenance Instructions 154394 en_GB 14 01 2019 A001 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www syste...

Отзывы: