6
3.2.4
Electrical data
Table 1 Power Consumption
Model
Fans (W tot.) 400 V
3N~
El Heating battery
(kW tot.)
Fuse (mains) (A) for
230V 1~ and 400 V 3N~
SC03 EL
1012
5
3x16
SC03 (None, HW)
1012
–
10
SC04 EL
1526
7.5
3x20
SC04 (None, HW)
1526
–
10
SC06 EL
2032
12
3x25
SC06 (None, HW)
2032
–
3x10
SC08 EL
3788
15
3x32
SC08 (None, HW)
3788
–
3x10
SC11 EL
6264
22.5
3x50
SC11 (None, HW)
6264
–
3x13
3.3
Transport and storage
The Topvex SC03-11 should be stored and transported in such a way that it is protected against physical damage that
can harm panels, handles, display etc. It should be covered so that dust, rain and snow cannot enter and damage the
unit and its components. The appliance is delivered with all necessary components, wrapped in plastic on a pallet for
easy transportation.
When transporting the Topvex SC03-11 units use a forklift placed on the gable of the unit. For size SC06-SC11 the units
are delivered in parts on the pallet.
Warning
• The unit is heavy. Be careful during transport and mounting. Make sure that proper lifting device is used.
Risk of injury through pinching. Use protective clothing.
• Be careful so the unit don't tip over.