background image

10

Installation

3.2.4

Residual current devices

Only universal (type B, B+) RCD protective devices are permitted.

Like frequency inverters, RCD protective devices cannot provide personal safety while operating the device, pulse
charge currents from the capacitors in the integrated EMC filter lead to the RCD protective device triggering without
delay.

We recommend residual current devices with a trigger threshold of 300mA and delay triggering. (super-resistant, char-
acteristic K)

3.3

Transportation and storage

All fans are packaged at the factory to withstand normal transport handling. When handling the goods use suitable lift-
ing equipment in order to avoid damage to fans and personnel. Avoid blows and shock loads. Store the fans in a dry
place protected from weather and dirt until final installation.

Warning

• The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use

protective clothing.

• Do not lift the fans by the connecting cable, connection box, motor bracket, impeller or inlet cone.

4

Installation

Danger

• Make sure that the mains supply to the unit is disconnected before performing any maintenance or

electrical work!

• All electrical connections must be carried out by an authorized installer and in accordance with local rules

and regulations.

Warning

• The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a

minimum 3 mm gap.

• Do not lift the fans by the connecting cable, connection box, motor bracket, impeller or inlet cone.

• Do not block or cover the drainage gap around the bottom of the fan.

The fan should be installed horizontally. Make sure the assembly of the fan is firmly fixed and stable. The fans must be
installed to ensure that service and maintenance can be performed easily and safely. Disturbing noise can be reduced
by installing silencers (available as an accessory). Electrical connections are made according to the wiring diagram in
the terminal box, markings on terminal blocks or on cable. All 3 phase fans are delivered from factory in 400 V 3~
connection.

206434 | A006

Содержание TFC 225 P

Страница 1: ...Document in original language 206434 A006 Roof fans TFC 225 560 S P Operation and Maintenance Instructions GB...

Страница 2: ...Systemair AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously...

Страница 3: ...3 Wiring diagram 6 3 2 4 Residual current devices 10 3 3 Transportation and storage 10 4 Installation 10 4 1 Installing the fans 11 4 2 Change from VAV to CAV 13 4 3 K factor 13 4 4 Commissioning 14 4...

Страница 4: ......

Страница 5: ...essment and risk reduction EN 13857 Safety of machinery Safety distances to prevent hazard zones being reached by upper or lower limbs EN 60 335 1 Household and similar electrical appliances Safety Pa...

Страница 6: ...ies Caution Indicates a risk of damaging the product or prevent optimal operation Important This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory...

Страница 7: ...ms The fans are meant for use in ducted systems and should always be duct connected on the inlet side No moving parts shall be accessible after installation TFC 225 560 S P roof fans are adapted to co...

Страница 8: ...B C D E F G H Weight kg TFC 225 413 422 281 330 435 266 49 195 12 4 TFC 280 514 523 333 450 535 368 86 245 17 1 TFC 355 618 627 376 535 637 491 150 300 27 5 TFC 450 728 737 417 655 747 602 176 375 35...

Страница 9: ...10V TFC 280 2 6V 0 0 4 0 8 1 2 1 6 0 250 500 750 1000 Q m s Ps Pa 0 1000 2000 3000 4000 5000 m h 16745 16744 5V 7 3V 10V TFC 355 2 5V 0 0 5 1 1 5 2 0 200 400 600 800 Q m s Ps Pa 0 2000 4000 6000 m h 1...

Страница 10: ...s possible from TFC 355 see wiring diagram Tacho 0 10V DC Ext RD YE BU WH 1 3 2 4 BU BN BK GN YE 230V 1 N L PE 1 TFC 225 280 S M RSA RSB 0 10V DC Ext RD YE BU WH BN 1 3 2 4 230V 1 BU BN GN YE N L PE G...

Страница 11: ...1 PE L3 GY BK BN GN YE 0 10V DC Ext RD YE BU WH BN RSA RSB WH 2 WH 1 BK 3 BK 2 BK 1 GN YE 1 TFC 500 S M 3 1 3 2 4 400V 3 5 6 BK BN GN YE GY C NC L3 L2 L1 PE L2 L1 PE L3 GY BK BN GN YE 0 10V DC Ext 10V...

Страница 12: ...N BK GN YE N L PE Tacho A GND US GND 1 2 TFC 225 280 P M 10V DC 10 24 V DC 2 1 Ri 4 k 1 3 2 4 230V 1 RD YE BU WH BN BU BN GN YE WH 2 WH 1 BU BK GN YE N L PE BU BN GN YE RSA RSB A GND US GND 1 2 1 2 TF...

Страница 13: ...4 400V 3 5 6 BK BN GN YE GY C NC L3 L2 L1 PE L2 L1 PE L3 GY BK BN GN YE 10V Ain1U GND RSA RSB A GND US GND 1 2 TFC 560 P M 3 10V DC 10 24 V DC 2 1 Ri 4 k 1 Safety switch 2 Fan control 3 Alarm RD Red...

Страница 14: ...ft the fans by the connecting cable connection box motor bracket impeller or inlet cone 4 Installation Danger Make sure that the mains supply to the unit is disconnected before performing any maintena...

Страница 15: ...cal compartment Figure 2 Connect the mains supply to the lockable safety switch 1 Image show S controller 2 The hinges on the hatch to the electrical compartment prevents the hatch from falling down F...

Страница 16: ...on 4 5 Figure 5 Mains supply 4 can be run through the cable glands beside the electrical compartment or inside a roof curb if used Note Don t cover this gap 5 It is for drainage if water enters the fa...

Страница 17: ...nection to the con troller the tubing from the bottom of the fan 1 to plus inlet and the tubing from the cone 2 to minus The tubing from the cone is labelled with blue tape In BASE SETUP 5 01 in table...

Страница 18: ...Rated current must not be exceeded with more than 5 at rated voltage The direction of rotation should correspond to direction of rotation arrow 3 phase Smoothness of motor operation no abnormal noise...

Страница 19: ...t for Escape Esc Info Selection of the menu group e g BASE SETUP to the right through the key to the left through the key You can go to the menu items in the menu groups e g mode by using the P key Us...

Страница 20: ...depending on adjusted setpoint and measured actual value Table 1 Parameter table Parameter Display Factory setting Function Mode 4 00 4 01 5 00 5 01 Mode INFO Information p 0 Pa 0 Pa Different actual...

Страница 21: ...01 0 100 sensor measuring range 5 01 0 Max Range qV depending on K factor and sensor measuring range 2 Small value quick regulation great value slow regulation high stability BASE SETUP Base setup Mod...

Страница 22: ...cessary at least once a year to avoid imbalance and unnecessary damage to the bearings The fan bearings are maintenance free and should only be replaced if damaged Do not use a high pressure cleaner s...

Страница 23: ...ce release the lock using the handle to bring the motor down Fasten the motor bracket with the screws Note TFC 225 and TFC 280 has no handle hold the motor bracket to lift the motor 7 Troubleshooting...

Страница 24: ...of fans Operation and Maintenance Instructions 206434 en_GB 21 11 2017 A006 Systemair Sverige AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99 www systemair co...

Отзывы: