17
SETTING 4.01 + 5.01
Setting
Setpoint 1
-
100 Pa
-
1185 m
3
h
Setpoint 1
1
Setpont 2
-
200 Pa
-
1185 m
3
h
Setpoint 2
,
2
(Active if voltage
at terminals 1, 2)
Pband
-
250 Pa
-
1185 m
3
h
Pband
Min. Uout
-
0.0 V
-
0.0 V
Min output
voltage:
0.0...10.0 V
(priority over
“Max. Uout”)
Parameter
Display/factory setting
Function
Max. Uout
-
10.0 V
-
10.0 V
Max. output
voltage:
10.0...0.0 V
1
Setting range 4.01: 0...100 % sensor measuring range, 5.01: 0...Max. Range qV (depending on K-factor and sensor measuring
range).
2
Small value = quick regulation, great value = slow regulation, high stability.
BASE SETUP
Base setup
Mode
4.00
4.01
5.00
5.01
Mode
Units
metric: Pa, m
3
/h, K-factor
SI units or
Imperial units
(US)
Measuring range
1: 0...1000 Pa
2: 0...500 Pa
3: 0...300 Pa
4: 0...200 Pa
PCA1000D2
Adjustable
measuring range
K-factor
(K-factor US)
-
-
75
75
Nozzle
coefficient (K-
factor) see
chapter 4.3
Autozero
OFF => ON
Automatic “0”
offset
Offset
0 Pa
Sensor offset
(automatically
when
“Autozero”)
Setting range:
+/- 1000 Pa