The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work
or constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or
a degradation with dangerous consequences for personnel and property. In such an event, the
warranty shall be null and void.
Caution
The unit base shall be arranged as indicated in the manual. There could be a risk of personal injury
or damage to property in the event of the unit being incorrectly supported.
Caution
Unit operation depends on air temperature. Any recycling of air extracted by the fan lowers the air
intake temperature across the exchanger fins and alters the standard operating conditions.
Caution
Do not expose the
SysAqua
to rejections from chimneys or vents. Fumes charged with soot or
grease as well as acid rejections are likely to clog or damage the condenser irreversibly. This would
cancel the warranty.
Caution
12 SysAqua
9. INSTALLATION
9.1. SITING THE INSTALLATION
The
SysAqua
must be installed outdoors with sufficient surrounding clearance to enable unobstructed air
circulation through the appliance and access for maintenance work.
In the case of the unit being sited in areas exposed to high winds, you must avoid the wind hitting the
fan blowing surface areas directly to avoid any risk of recycling cooled air. Exchanger fan operation can be
disrupted by strong winds, which can cause de-icing problems and fan malfunctions.
Depending on temperature and outdoor air humidity conditions, water vapour contained in the air can
condense on the finned heat exchanger and even form ice under low outdoor temperature conditions (around
< 5°C). This condensate water and defrosted water runs off via outlets provided under the exchanger. To aid
water run-off and avoid frozen water remaining in the appliance in winter, we recommend that it is mounted
at a height of around 10cm off the ground. In this way, condensate and defrosted water can run off freely
and be absorbed into the ground or channelled to a basin built under the appliance in order to protect the
environment.
In areas where outdoor temperatures fall below 1°C, the system can be equipped with a condensate anti-
freeze protection system (e.g. a heated pipe sheath, Not supplied).
In order to contain noise levels, we equip our appliances with quiet fans and encase the technical compartment
in sound-proofed panels. However, noise levels can be reduced even further by following a few installation
precautions:
²
Do not install the appliance near a window.
²
Do not install the unit in enclosed or confined yards, narrow locations where noise may be reflected
on walls
²
Avoid locating the appliance in a corner (increased reverberated noise).
²
Install the rubber pads supplied or anti-vibration pads (available as an option) under the appliance.
²
Do not join the concrete slab supporting the appliance to the structure of the dwelling (structure-
borne noise transmission).
²
Electrical and hydraulic connections to the unit must be flexible to avoid transmitting vibrations.
9.1.1. PREVAILING WIND
9.1.2. CONDENSATE WATER MANAGEMENT IN HEATING MODE
9.1.3. HOW TO REDUCE NOISE POLLUTION