13.5. ALARMS MANAGEMENT AND DISPLAY
13.5.1. HIGH PRESSURE ALARM
When this alarm is triggered, the control system causes the refrigerating circuit to stop and opens the
compressor control chain (safety against failures).
The alarm is reset by the pressure switch and manually bu OFF mode
13.5.2. LOW PRESSURE ALARM
When this alarm is triggered, the control system causes the refrigeration circuit to stop. The operation of
this alarm is delayed for about 30 seconds after the start-up.
The alarm is auto reset 2 time then manual.
13.5.3. ANTIFREEZE ALARM (COOLING MODE)
It is triggered when the temperature of the fluid leaving the evaporator drops below 4°C. When this alarm
is triggered, the control system causes the refrigerating circuit to stop.
The alarm is manually reset from the control panel.
The protection by pressure is activated when the pressure is less than 6.8 bars (when no glycol is used). The
protection reset is automatic. This value is automatically modified if the pourcentage of glycol parameter is
modified by the GLY parameter. Refer to the §
13.5.4. MENUS ALAR AND LOG
The ALAr menu is intended to display the active alarms of the unit. Several alarms may be active at the
same time. The alarms are recorded in a permanent memory. The LOg menu is intended to display the latest
10 alarms which have been recorded.
code
Alarm description
Réarmement
notes
auto
manual
ADC
Microprocessor error
CPF
High pressure transducer failure, out of range
EPF
Low pressure transducer failure, out of range
REF
Refrigerant leak - low pressure
CPnc
High pressure transducer failure, pressure unchanged
EPnc
Low pressure transducer failure, pressure unchanged
CFC1
Compressor 1 failure
wrong rotation
CFC2
Compressor 2 failure
wrong rotation
EWTH
Return water feeler failure
Court-circuit
EWTL
Return water feeler failure
Non connectée
LWTC
No outlet water temperature change
LWTH
Outlet water feeler failure
short-circuit
LWTL
Outlet water feeler failure
not connected
DISH
Compressors delivery temperature feeler failure
short-circuit
DISL
Compressors delivery temperature feeler failure
not connected
OATH
Air temperature feeler failure
short-circuit
OATL
Air temperature feeler failure
not connected
OC1H
Battery 1 temperature feeler failure
short-circuit
OC1L
Battery 1 temperature feeler failure
not connected
OC2H
Battery 2 temperature feeler failure
short-circuit
OC2L
Battery 2 temperature feeler failure
not connected
HPP
First high pressure protection
Stop 1 compresseur
HP
High pressure protection
auto reset 3 times
HPC
High pressure protection - high pressure switch
LP
Low pressure protection
auto reset 3 times
DIS
Compressors delivery temperature too high
LFP
Cool mode freeze protection by pressure
LO
Outlet water temperature too low
auto reset 3 times
HI
Inlet water temperature too high
FS
Differential water flow or pressure switch
CF1
Compressor 1 thermal load protection
CF2
Compressor 2 thermal load protection
OF1
Fans thermal load protection
PF
Pump thermal load protection
LOu
Low water volume
EEP
Microprocessor error
JUMP
Wrong DIP configuration
check DIP
ConF
Wrong configuration