26 SysAqua
13.1.4. FUNCTION OF DSW2 DIP SWITCHES
DIP OFF
ON
DEFAULT
1
OFF mandatory
2
Not used
ON mandatory
ON
3
Auto changeover ON
Auto changeover OFF
ON
4
OFF = Compressors do not stop
after deice
ON = Compressors stop after
deice
ON mandatory
5
Only cold
Heat pump
Only cold = OFF
Heat pump = ON
6
Not used
R410A
ON
7
One coil
Two coils
OFF: SysAqua 25/30/35/40/45/55
ON: SysAqua 65/75/90/105/125
8
Not used
Not used
OFF
13.2. KEYBOARD
Position
0
: OFF mode : pump and frost protection heaters will run if required. Test mode is possible.
Position
1
: ON mode : Test mode is possible.
There are two menu levels :
²
Standard parameters that can be modified
²
Factory parameters
protected by a password.
The standard parameter menu can be entered by pressing both buttons for 5seconds.
The menu returns to normal mode if you do not press any button for 10s.
The parameters can be scrolled by pressing the button
and then selected by pressing
.
After having selected the parameter, it is possible to change the value by using the button
. The value
is scrolled from its minimum to maximum value. To enter the modified value press the button
.
Touche
: To scroll the MENUS horizontally and to display the values of parameters..
Touche
: To scroll the MENUS and SUBMENUS vertically and to increase the numeric value of parameters.
All information is displayed on 4 7-segment displays.
The heat and cool setpoint s can be modified in the standard parameter
menu.
13.2.1. SWITCH SM1
13.3. DISPLAY