Component position and description cont'd
Position
Description
6.
Fire/smoke damper B
7.
Fire/smoke fan
8.
Compressor
9.
Condenser
10.
Expansion valve
11.
Sight glass
12.
Filter dryer
13.
Water pump
HPT
Refrigerant High pressure sensor
LPT
Refrigerant Low pressure sensor
LTT
Refrigerant suction gas temperature sensor
HTT
Refrigerant discharge gas temperature sensor
WTT1
Water in temperature sensor
WTT2
Water out temperature sensor
HPZ
Refrigerant High pressure safety switch
LPZ
Refrigerant Low pressure safety switch
FAPdC
Fan differential air pressure sensor
SFDT
Smoke and fire sensor
ATT1
Extract air temperature sensor
ATT2
Exhaust air temperature sensor
FIPdT
Filter air pressure sensor
ATT
Ambient temperature sensor
WFZ
Water flow switch
DUPdT
Duct differential air pressure transmitter
DAAE
Extract air damper actuator
DAAS
Fire/Smoke damper actuator
DAAH
Exhaust air damper actuator
ABHS
Apartment building heating system
4.2 General Description
The Living HP is extract air ventilation unit with integrated heat pump section to recover heat from extract
air and deliver heat to building heating system. The Living HP unit should be integrated in building extract
air ventilation system and is designed to control fire/smoke fan during normal operation.
The stops and starts of the unit are based on the ambient air temperature. The default value set to
start the unit is +15°C. This value can be changed in the control panel. Other conditions which should
be met for the heat recovery to start:
• water flow should be more than 0,5 m³/h
• extract air temperature should be more than +10°C
• air pressure drop should be more than 30 Pa
These values can also be changed in the control menu.