4.7.6 Filters
Living HP comes with the pair of class M5 filters and G4 pre-filters installed in the factory. Filters are used
to filter extracted air from the residence in order to prevent dust gathering on components inside of the
unit. Filters need to be replaced when polluted. New sets of filters can be acquired from your installer or a
wholesaler. Optionally, filter quality F7 can be installed for extract air filtering.
The filter type is labelled on the top of the filter.
4.7.7 Damper
The function of the damper is to direct the airflow. When the unit is off, extract damper A and exhaust
damper C are closed and the Fire/Smoke damper B is open to make air flow directly to the outside. When
the unit is operating, extract and exhaust dampers are open and the Fire/Smoke damper is closed to make
air flow through the unit. For more information see chapter 4
4.7.8 Drip tray
The drip tray is located under the evaporator/brine coil and collects the water condense that periodically
occur during the cooling operation. The drip tray is made of stainless steel and has a 32 mm connection
for connecting the drain pipe. The drip tray has an electrical heater to prevent the water condense from
freezing.
Operation and Maintenance Instructions
209531
9
Systemair AB